Chapter 1 Introduction
Accura 2300/2350 User Guide
Page 24
ⓒ
2011 Rootech Inc. All Rights Reserved
Accura 2300/2350-3PSC[1PSC, 1PSCSH] Split-core Power Measuring Module
Split-core power measuring module is a core separation structure, so it can be installed in live state without
power interruption. The following is an example of installing the split-core power measuring module used in
the distribution board[or switchboard]
Fig 1.5 Split-core Power Measuring Module InstallationExample
1. Split-core single-phase single-hole power measuring modules can be used in three-phases by installing one module per
phase [A, B, C] and grouping them. In the case of three-phase three-wire connection, it is possible to measure three-phases
only by installing two modules on phase A and phase C.
2. Packaged with device. Core conductor of 6C telephone line should be minimum 0.128mm
2
[26 AWG]. It is recommended
that distance from power line is 5mm or more so that interference caused by noisy power line will not occur.
3. Ethernet communication is for dedicated communication with upper program.
Note
Accura 2350-1PSCSH Split-core single-phase single-hole power measuring module is recommended in the
following cases.
-
Through-hole current exceeds 250A
-
Difficult to make through-hole wiring because of a large gap between busbars[or cables]
Installation
Front panel
Accura 2300
Distribution panel digital power meter
Incoming feeder
Accura 2350-1PSCSH
1
Split-core single-phase single-hole power measuring module
Branch load
Accura 2350-3PSC
Split-core three-phase power measuring module
Accura 2350-1PSC
Split-core single-phase power measuring module
Communication
6C telephone line
2
Only for internal communication
Ethernet
3
Only for external communication
[three-phase 3-wire]
[three-phase 4-wire]
Содержание Accura 2300 Front