Maintenance
B0048991 / Rev. 1.3
108
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
10.2 Exchange of control unit
Exchange with help of the RPP-software (only with C-versions):
The UDK20 provides for backup and re-writing the equipment parameters via the RS232 interface,
with help of the provided RPP-software.
Exchange without help of the RPP-software:
After exchanging the equipment, the original system configuration must be restored. Therefore, the
form „System Configuration“ in chapter „Technical Documents“ (which had been filled out during
set-up) can be used. If this form is not available or filled out, the information on the system
configuration must be retrieved from the equipment documentation.
10.3 Replacement of fuses
Attention
The fuse should be checked only by trained personnel,
since it is necessary to open the control unit.
The power supply fuse is 5 x 20 mm, 3,15 Amp slow blow. A spare fuse is accommodated in the
control unit. The position of the spare fuse is shown in the picture below.
14 13 12 11 10 9 8 7 6 5 4 3 2 1
18 17 16
20 21
36 37 38 39
35
34
33
32
31
30
29
28
27
26
25
24
23
22
19
40 41 42 43 44 45 46 47 48
Ansicht: Nach unten geklapptes Oberteil
View: Top part flipped down
1
4
3
5
2
1 Fuse
2 Spare fuse
(3,15 A medium-blow)
3 Terminal blocks
4 Enclosure lid
5 Cover
Fig. 80: Position of fuses in the UDK20