Manual
Double Sheet Detector R1000 series UDK20
B0048991 / Rev. 1.3
Fault messages, causes and remedies
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
105
9.8
Faults concerning supply voltage
No.
Cause
Remedy
60
Operating voltage was below 20 VDC.
Check power supply.
62
Sensor voltage too low.
Check external power supply
(insufficient power ?).
Contact Roland Electronic Service Department.
9.9
Faults Sensor Switch Box
No.
Cause
Remedy
65
Error in the Sensor Switch Box.
If a Sensor Switch Box is connected, check box and
cables.
Otherwise read the notes in chapter 9.1.
9.10 Faults concerning PLC parallel inputs
No.
Cause
Remedy
70
Operation of PLC inputs is incorrect.
Check timing of PLC inputs.
71
The parallel function is not possible, because
another parallel function is active (e.g. measurement
start and in addition Teach-In 1-sheet).
See timing diagrams.
72
Selected program number >255.
Select the new program number.
73
Parallel function is blocked in the system
configuration (ext. adjust: no).
If required, change configuration.
76
The parallel function is not possible, because the
system was configured to “internal control”.
In case of “internal control” it is only possible to select the
measuring program. If required, change configuration to
“external control”.
77
The parallel function is not possible, because the
menu is open.
Close the menu.
9.11 Other faults
No.
Cause
Remedy
> 80
An error has occurred which cannot be
unequivocally identified to one of the above error
codes.
Contact Roland Electronic Service Department.