Double Sheet Detector R1000 series UDK20
Electrical installation
B0048991 / Rev. 1.3
56
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
5.2.2 Sensor connection – 2nd sensor
The connection for the 2nd sensor is
only
present at unit versions
UDK20-2PW-x-x-S(-FP)
,
but not at unit versions UDK20-x-x-S(-FP).
Connection of the sensor to the control unit
with the cable
"SCPWS-GG or SCPWS-GW"
.
2
3
4
5
6
8
7
9
grey
pink
red
black
violet
blue
brown *
white *
brown
green
UD
K2
0
1
2
3
4
5
6
8
7
9
Se
ns
or
PW
42
A
G
S
43
44
40
41
42
47
48
45
46
Sensor
plug
* 1 mm²
Sensor cable pin
Meaning
Colour of wire
Terminal no. of control unit
Pin 1
W-In 1
grey
43
Pin 2
W-In 2
pink
44
Pin 3
+12 VDC
red
40
Pin 4
0 VDC
black (black/violet in sensor cable)
41
Pin 5
-12 VDC
blue
42
Pin 6
P-line 1
brown 1 mm²
47
Pin 7
W-Out 1
brown
45
Pin 8
P-line 2
white 1 mm²
48
Pin 9
W-Out 2
white
46