Rockwell Automation Publication 2715P-UM001C-EN-P - March 2019
71
Monitor and Manage Control System Alarms
Chapter 4
Enable
Enables the selected alarms in the alarm manager table, which allows the
alarm condition to be evaluated, which turns on the alarm. An enabled alarm
enables all conditions for that alarm. You cannot enable an individual alarm
condition.
Faulted
Provides a count of the alarms in a faulted state.
Help
Provides a description of the help buttons and alarm status.
In Alarm, Acked
(acknowledged)
Provides a count of the alarms in an acknowledged state.
In Alarm, Unacked
(unacknowledged)
Provides a count of the alarms in an unacknowledged state.
Normal, Unacked
Provides a count of the alarms where the input of the alarm has returned to
normal, but the alarm has not yet been acknowledged.
Pause
Stops updates to the alarm summary table for 10 seconds, or until another
operation is performed on the table. While updates to the alarm summary
table are paused, alarms in the controller are still evaluated. When the table is
no longer paused, any changes to alarm states are reflected in the table and
updates resume.
Reset Counts
Resets the alarm count in the controller and the alarm count value in the
details pane of the alarm manager table to zero. The reset is performed for all
conditions of the currently selected alarm.
Reset Latched
Sets the selected digital latched state of the alarm to normal if the input of the
alarm has returned to normal. A reset of a digital latched alarm acknowledges
the alarm, if it is not acknowledged.
Select All
Selects all alarms in the alarm table, including the alarms that are not
displayed on the current page of alarms.
Select Page
Selects all alarms that are displayed on the current page of alarms.
Shelve
Helps prevents the notification of new state changes to the selected alarm if
the alarm is acknowledged. Updates to the alarm do not appear. The alarm
remains shelved until the shelve duration from the controller expires
automatically or you unshelve the alarm manually. Updates to the alarm then
resume.
When you shelve an alarm in the alarm summary table, you shelve only the
selected alarm conditions. When you shelve an alarm in the alarm manager
table, you shelve all conditions of the alarm. From the condition list in the
details pane of the alarm manager table, you can also shelve individual alarm
conditions.
Unshelve
Unshelves the selected alarm in the alarm manager table, which allows
notification of new state changes to alarms. From the condition list in the
details pane of the alarm manager table, unshelve individual alarm
conditions.
Table 19 - Alarm Function Key Descriptions (Continued)
Symbol
Function Key or
Message
Description
Содержание Allen-Bradley PanelView 5510 Series
Страница 6: ...6 Rockwell Automation Publication 2715P UM001C EN P March 2019 Table of Contents Notes...
Страница 10: ...10 Rockwell Automation Publication 2715P UM001C EN P March 2019 Preface Notes...
Страница 86: ...86 Rockwell Automation Publication 2715P UM001C EN P March 2019 Chapter 5 Install and Replace Components Notes...
Страница 92: ...92 Rockwell Automation Publication 2715P UM001C EN P March 2019 Chapter 6 Update Firmware Notes...
Страница 108: ...108 Rockwell Automation Publication 2715P UM001C EN P March 2019 Index Notes...
Страница 109: ...Rockwell Automation Publication 2715P UM001C EN P March 2019 109 Index Notes...
Страница 110: ...110 Rockwell Automation Publication 2715P UM001C EN P March 2019 Index Notes...
Страница 111: ......