Publication 2094-UM001A-EN-P — September 2006
222
Upgrading Firmware
7.
The Update Status dialog opens and indicates success or failure as
described below.
8.
Select OK.
The ControlFLASH software returns to the Welcome screen where
you can flash another drive or select Cancel to exit the program.
Troubleshooting ControlFLASH
If your Update Status dialog in Step 7 indicated failure, check the
following items and begin the process again at Step 1:
•
Control (24V) power lost at drive.
•
SERCOS ring is down (seven-segment LED no longer displays
fixed 2, 3, or 4).
•
Logix chassis lost power.
•
Bad flashdata checksum.
Flashing
If
Succeeded
1. Update complete appears in a GREEN status dialog.
2. Go to Step 8.
Failed
1. Update failure appears in a RED status dialog.
2. Go to Troubleshooting ControlFLASH.
Содержание Allen-Bradley Kinetix 6000
Страница 8: ...Publication 2094 UM001A EN P September 2006 8 Table of Contents...
Страница 18: ...Publication 2094 UM001A EN P September 2006 18 Start...
Страница 118: ...Publication 2094 UM001A EN P September 2006 118 Connecting the Kinetix 6000 Drive System...
Страница 144: ...Publication 2094 UM001A EN P September 2006 144 Configure and Startup the Kinetix 6000 Drive System...
Страница 168: ...Publication 2094 UM001A EN P September 2006 168 Removing and Replacing the Kinetix 6000 Drive Modules...
Страница 190: ...Publication 2094 UM001A EN P September 2006 190 Specifications and Dimensions...
Страница 256: ...Publication 2094 UM001A EN P September 2006 256 Integrating Resistive Brake Modules with Kinetix 6000 Drives...
Страница 265: ...Publication 2094 UM001A EN P September 2006 265 Notes...
Страница 266: ...Publication 2094 UM001A EN P September 2006 266 Notes...
Страница 267: ...Publication 2094 UM001A EN P September 2006 267 Notes...