Publication 2094-UM001A-EN-P — September 2006
136
Configure and Startup the Kinetix 6000 Drive System
3.
Observe the IAM/AM logic power LED indicator.
4.
Determine your source of three-phase input power.
Seven-segment
Fault Status LED Indicator
Logic Power
LED Indicator
If the Logic Power LED Indicator is
Then
ON
Go to Step 4.
Not ON
1. Check your control power connections.
2. Go back to main Step 2.
If Your Three-phase
Power
Then
Is sourced from a LIM
1. Set CB1 to the ON position.
2. Verify the Hardware Enable Input signal (IOD pin 2) for each
axis is at 0 volts.
Remove the connection between IOD-1 and IOD-2 if one exists.
3. Go to main Step 5.
Is not sourced from a LIM
1. Apply 195...265V ac (230V) or 324...528V ac (460V) input power
to the IAM (IPD connector).
2. Verify the Hardware Enable Input signal (IOD pin 2) for each
axis is at 0 volts.
Remove the connection between IOD-1 and IOD-2 if one exists.
3. Go to main Step 5.
Содержание Allen-Bradley Kinetix 6000
Страница 8: ...Publication 2094 UM001A EN P September 2006 8 Table of Contents...
Страница 18: ...Publication 2094 UM001A EN P September 2006 18 Start...
Страница 118: ...Publication 2094 UM001A EN P September 2006 118 Connecting the Kinetix 6000 Drive System...
Страница 144: ...Publication 2094 UM001A EN P September 2006 144 Configure and Startup the Kinetix 6000 Drive System...
Страница 168: ...Publication 2094 UM001A EN P September 2006 168 Removing and Replacing the Kinetix 6000 Drive Modules...
Страница 190: ...Publication 2094 UM001A EN P September 2006 190 Specifications and Dimensions...
Страница 256: ...Publication 2094 UM001A EN P September 2006 256 Integrating Resistive Brake Modules with Kinetix 6000 Drives...
Страница 265: ...Publication 2094 UM001A EN P September 2006 265 Notes...
Страница 266: ...Publication 2094 UM001A EN P September 2006 266 Notes...
Страница 267: ...Publication 2094 UM001A EN P September 2006 267 Notes...