Rockwell Automation Publication 7712-UM001D-EN-P - October 2017
65
Troubleshooting
Appendix C
Door to Isolation Shutter
1. Open the LV door.
2. Remove the four M6 bolts located on the compartment floor
(
Figure 44
).
Figure 44 - Circumvent Door to Isolation Shutter, Removing the bolts
ATTENTION:
This procedure requires contact with medium voltage
components. To avoid shock hazards, complete the Power Lockout procedure
on
before servicing the equipment. Verify with a hot stick or
appropriate voltage measuring device that all circuits are voltage free. Failure
to do so may result in severe burns, injury or death.
WARNING:
Use suitable personal protective equipment (PPE) per local
codes or regulations. Failure to do so my result in severe burns, injury, or
death.
IMPORTANT
Before circumventing door to isolation shutter interlock:
• The contactor cart must be fully withdrawn.
• Earthing switch must be closed.
Содержание Allen-Bradley 7712
Страница 6: ...6 Rockwell Automation Publication 7712 UM001D EN P October 2017 Table of Contents Notes ...
Страница 10: ...10 Rockwell Automation Publication 7712 UM001D EN P October 2017 Preface Notes ...
Страница 14: ...14 Rockwell Automation Publication 7712 UM001D EN P October 2017 Chapter 1 General Information Notes ...
Страница 24: ...24 Rockwell Automation Publication 7712 UM001D EN P October 2017 Chapter 3 Start up Procedure ...
Страница 25: ...Rockwell Automation Publication 7712 UM001D EN P October 2017 25 Start up Procedure Chapter 3 ...
Страница 26: ...26 Rockwell Automation Publication 7712 UM001D EN P October 2017 Chapter 3 Start up Procedure ...
Страница 36: ...36 Rockwell Automation Publication 7712 UM001D EN P October 2017 Chapter 4 Equipment Operation Notes ...
Страница 58: ...58 Rockwell Automation Publication 7712 UM001D EN P October 2017 Chapter 5 Maintenance Notes ...
Страница 73: ......