Rockford Systems, LLC
1-800-922-7533 (U.S.A. only)
25
Press
ENTER
to go into the submenu.
P2 SAFETY DEVICE METHOD
The display reads:
P2 SAFETY DEVICE METHOD
TWO-HAND, OTHERS
This is the factory setting. To change the factory setting,
press
ENTER
and the display reads:
P2 SAFETY DEVICE METHOD
LIGHT CURTAIN (If this setting is
chosen, follow the ALTERNATE SETTING
PROGRAMMING in the right column.)
Press
▼
to go to the next setting.
P2 APPROACH SPEED
(Hand Speed Constant)
The display reads:
P2 APPROACH SPEED 063 IN/S
This is the factory setting. To change the factory setting,
press
ENTER
and the display reads:
P2 APPROACH SPEED 079 IN/S
Press
ENTER
again and the display reads:
P2 APPROACH SPEED 087 IN/S
Continue to press
ENTER
until the desired setting is
displayed. Press
▼
to select it and go to the next setting.
P2 QUIT
The display reads:
P2 QUIT
Press
ENTER
to quit the Parameter 2 submenu and to
return to the M
M PARAMETER 2 SAFETY DISTANCE.
Press the
▲
or
▼
buttons to go to the next
MM
program
that requires programming or go to the
MM STOP-TIME
MEASURING
program to do a test.
ALTERNATE SETTING PROGRAMMING
After selecting
P2 SAFETY DEVICE LIGHT
CURTAIN
,
press
▼
to go to the next setting.
P2 RESPONSE TIME
The display reads:
P2 RESPONSE TIME CURTAIN 000MS
This is the factory setting for the response time. To
change the factory setting, press
ENTER
. The display
reads:
P2 RESPONSE TIME CHANGE 000MS
Use the
▲
or
▼
buttons to scroll through the numbers
000 - 255 MS
. Press
ENTER
at the desired selection and
the display reads:
P2 RESPONSE TIME CURTAIN XXXMS
(XXX = the programmed response time)
Press
▼
to go to the next setting.
P2 RESOLUTION
(Minimum Object Sensitivity)
The display reads:
P2 RESOLUTION CURTAIN 00.0IN
This is the factory setting. To change the factory setting,
press
ENTER
. The display reads:
P2 RESOLUTION CHANGE 00.0IN
Use the
▲
or
▼
buttons to scroll through the numbers
00.0 - 10.0 IN
. Press
ENTER
at the desired selection.
The display again reads:
P2 RESOLUTION CURTAIN XX.XIN
(XX.X = the programmed resolution)
Press
▼
to go to the next setting.
P2 APPROACH SPEED
- See instructions in left column.
MM PARAMETER 2
SAFETY DISTANCE
SECTION 5—PROGRAMMING
Stop-Time Measurement Device
(Continued on next page.)