- 42 -
<Contact Activation>
The contact is activated when the gas concentration reaches or exceeds the alarm setpoint. The contact
activation is reset automatically when the gas concentration drops below the alarm setpoint.
<Contact Activation (Auto-reset)>
In case of Auto-reset setting, the contact is activated when the gas concentration reaches or exceeds the
alarm setpoint value. The contact activation is reset automatically when the gas concentration drops below
the alarm setpoint value.
NOTE
In DETECTION MODE, select and press one of the following key to reset : “MODE”, “
▲
”, “
▼
” or
“TEST/SET”.
"Alarm Pattern (H-HH)"
Содержание GD-70D Series
Страница 15: ... 15 GD 70D Tubing Diagram ...
Страница 43: ... 43 GD 70D Alarm Pattern L H Alarm Pattern L LL oxygen deficiency alarm ...
Страница 45: ... 45 GD 70D Alarm Pattern L H ...
Страница 58: ...GD 70D 58 Return to Detection Mode Press the TEST key for 3 seconds ...