GD-70D
- 22 -
5. Attach the mounting plate to the installation surface using two or three M5 screws.
Recommended mounting screw (M5)
Length of 8 mm or more
Flat washer of φ10 mm or less (small round)
6. Leave the main unit detached from the mounting plate and continue to the wiring section.
4-6
Wiring the Detector
NOTE
To use the pyrolyzer unit (PLU-70), also refer to the separate operating manual.
<Recommended Cable>
For 3-wire type (common cable for
power and signal) (4 - 20 mA/EA
specification)
Shielded cable of CVVS, etc. (1.25 mm
2
) - 3-core
For 2-wire type (power and signal
cables separated) (4 - 20 mA/EA
specification)
Power: Cable of CVV, etc. (1.25 mm
2
) - 2-core
Signal: Shielded cable of CVVS, etc. (1.25 mm
2
) - 2-core
For 2-wire type DC power-line
communication system (NT
specification)
Shielded twisted-pair cable of KPEV-S, etc. (1.25 mm
2
) -
1P
For Ethernet (EA)
Power: Cable of CVV, etc. (1.25 mm
2
) - 2-core
Signal: Ethernet cable (category 5 or higher)
For PoE (EA)
Ethernet cable (category 5 or higher)
For LONWORKS output cable
Shielded twisted pair cable of KPEV-S, etc. (1.25 mm
2
)
・
1P
For contact
Cable of CVV, etc. (1.25mm
2
) - max. 6-core
CAUTION
•
Be careful not to damage the internal electronic circuit when wiring. In addition, be careful to provide
appropriate strain relief when using cables for wiring.
•
The power cables and signal cables must not be installed together with the motor power cables, etc.
When these cables must be installed together for unavoidable reasons, put the power cables and
signal cables in a metal conduit. The conduit must be connected to a grounding circuit.
•
When stranded wires are used, prevent wires from contacting each other.