INSTALLATION
Installation Instructions for SIS Bus Bar Systems A2MS001EN revision R05
45 / 130
Fig. 17: Marking the bolted connection
7.
Mark the checked bolted connections with a red
paint pen to indicate they have been completed (
Fehler! V
erweisquelle konnte nicht gefunden werden.
).
4.5
INSTALLING BUS BARS
4.5.1
SPACING BETWEEN BAR
ELEMENTS
Correct Spacing
………………………
Fig. 18: Spacing between bars 80 mm or 100 mm, depending on
the specific order, tolerance
± 20 mm
In order to make a perfect connection between the
bars possible, the flat terminals must be aligned on
both axis.
The spacing between bars has to be 80 mm or
100 mm, depending on the specific order. The exact
spacing is stated in the specific order documents.
RITZ Instrument Transformers GmbH allows a
maxim
um tolerance of ± 20 mm (
) for the above
specified dimensions.
Deviations within the tolerance of these dimensions
have to be documented in the assembly drawing.
Deviations outside of the tolerance are not permitted!