FAMILY
24
5.16 Error history
The
ERROR HISTORY
function is automatically enabled only after the machine has been
powered up for at least 2 consecutive hours, during this period of time any alarms that arise
would not be saved in the “error history”. The alarms can be displayed in chronological
order, from the most recent to the oldest, up to a maximum of 50 alarms; to display the
error history:
-
access the technical parameters as explained in the section “Accessing the technical
parameters”
-
select
ERROR HISTORY
with the “
UP
” and “
DOWN
” keys, confirming the selection
EXHAUST PROBE RESET
COMBUSTION ANALYSIS
CALIBRATION
RANGE RATED
ERROR HISTORY
INSTALLER
TECHNICAL
-
scroll through the alarms log with the “
UP
” and “
DOWN
” keys; for each alarms a
sequential number is displayed, an error code and the date and time the alarm occurred.
FAN ERROR
1 - 10:30 18/11/2013
E030
USE ARROW KEYS TO SEE OTHER ANOMALIES
It is possible to return to the start page at any time by keeping the “
BACK
” key pressed for
at least 2 seconds.
Note
: Once enabled, the ERROR HISTORY
function can no longer be disabled; there is no
procedure for resetting the error history.
If an alarm repeats consecutively, it is saved only once.
5.17 Temporary switch-off
In the event of temporary absences (weekends, short breaks, etc.) set the status of the
boiler to OFF
.
OFF
HOT WATER ONLY
HEATING AND HOT WATER
BOILER
While the electrical supply and the fuel supply remain active, the boiler is protected by the
systems:
-
heating anti-freeze
: this function is activated if the temperature measured by the flow sensor
drops below 5°C. A heat request is generated in this phase with the ignition of the burner at
minimum output, which is maintained until the outlet water temperature reaches 35° C;
-
domestic hot water anti-freeze
: this function is activated if the temperature measured
by the domestic hot water probe drops below 5°C. A heat request is generated in this
phase with the ignition of the burner at minimum output, which is maintained until the
outlet water temperature reaches 55° C.
b
The activation of the ANTI-FREEZE function is indicated by a scrolling message on
the foot of the REC10 display.
-
circulator anti-locking
: the circulator activates every 24 hours of stoppage for 30
seconds.
5.18 Switching off for lengthy periods
The long term non use of the
Family
boiler causes the following operations to be carried out:
-
set the status of the boiler to
-
set the system’s main switch to “off”
-
close the fuel and water taps of the heating and domestic hot water system.
In this case, the anti-freeze and anti-blocking systems are deactivated. Drain the heating
and domestic water system if there is any risk of freezing.
OFF
HOT WATER ONLY
HEATING AND HOT WATER
BOILER
Closing
position
ON
OFF
5.19 System reset
b
This operation must be carried out only by professionally qualified personnel.
Whenever necessary, it is possible to restore the factory settings by carrying out a SYSTEM
RESET:
-
access the technical parameters as explained in the section“ Accessing the technical
parameters”
-
select INSTALLATION with the “
UP
” and “
DOWN
” keys, confirming the selection
RANGE RATED
WEATHER COMPENSATION
PARAMETERS
CALIBRATION
INSTALLATION
INSTALLER
TECHNICAL
-
select SYSTEM RESET with the “
UP
” and “
DOWN
” keys, confirming the selection
ZONES MANAGER
SENSOR CALIBRATION
SYSTEM RESET
INSTALLER
INSTALLATION
-
select CONFIRM to confirm the system reset or else CANCEL to cancel the operation
.
CANCEL
CONFIRM
Note:
After a reset it is necessary to carry out a new configuration of the system; for details
about this procedure, see the following section.
5.20
System configuration
b
This operation must be carried out only by professionally qualified personnel.
When restarting after a replacement of the REC10 rather than after a “SYSTEM RESET”,
the remote control an initial screen with the firmware revision. Pressing “
ENTER
” starts a
guided procedure for configuring the system; select the desired options with the “
UP
” and
“
DOWN
” keys, confirming the selection
:
PRESS ANY KEY TO CONTINUE
REC10R
R02.06
Welcome home
-
LANGUAGE selection:
ENGLISH
-
setting TIME and DATE