FAMILY
14
MENU
DEFAULT VALUE
FACTORY SET
MINIMUM
VALUE
MAXIMUM
VALUE
ACCESS LEVEL
NOTES
SET
VALUE
FUNCTION DISABLED
SERVICE
STOP FUNCTION
INSTALLER
Only if VENT CYLCE in
progress
EXHAUST PROBE RESET
INSTALLER
ADD WATER TANK
INSTALLER
Only in instantaneous
confi guration
WATER TANK
INSTALLER
REMOVE WATER TANK
INSTALLER
WATER TANK SETPOINT
50 °C
37,5 °C
60 °C
INSTALLER
Only if HEAT PUMP enabled
to DHW
TANK FROST PROTECT
7 °C
0 °C
100 °C
SERVICE
Only if HEAT PUMP enabled
to DHW
TANK FR PROT OFFSET
5 °C
1 °C
20 °C
SERVICE
Only if HEAT PUMP enabled
to DHW
ADD SOLAR PLANT
INSTALLER
Only if solar system is not
confi gured
SOLAR
INSTALLER
REMOVE SOLAR PLANT
INSTALLER
T MAX TANK
60 °C
10 °C
130 °C
INSTALLER
DELTA T ON PUMP
8 °C
DELTA T OFF
PUMP
30 °C
INSTALLER
DELTA T OFF PUMP
4 °C
4 °C
DELTA T ON
PUMP
INSTALLER
INTEGRATION DELAY
0 min
0 min
199 min
INSTALLER
COLLECTOR T MIN
(--)
(--) / -30 °C
0 °C
INSTALLER
COLLECTOR T MAX
110 °C
COLLECTOR T
PROT
180 °C
INSTALLER
COLLECTOR T PROT
110 °C
80 °C
COLLECTOR T
MAX
INSTALLER
COLLECTOR T AUTH
40 °C
COLLECTOR T
LOCK
95 °C
INSTALLER
COLLECTOR T LOCK
35 °C
-20 °C
COLLECTOR T
AUTH
INSTALLER
PWM COLL PUMP
0 min
0 min
30 min
INSTALLER
TANK COOLING
FUNCTION NOT
ACTIVE
FUNCTION NOT
ACTIVE
FUNCTION
ACTIVE
INSTALLER
SOLAR PUMP MODE
OFF
OFF / ON / AUTO
INSTALLER
ADD HEAT PUMP
INSTALLER
Only if heat pump not
confi gured
HEAT PUMP
INSTALLER
REMOVE PDC
INSTALLER
Only if heat pump not
confi gured
USE FREE CONTACTS /
USE BUS
USE BUS
USE BUS
USE FREE
CONTACTS
SERVICE
ENABLE COOLING /
DISABLE COOLING
DEACTIVATE
FUNCTION
FUNCTION
ACTIVE
DEACTIVATE
FUNCTION
INSTALLER