Distance Relay Setting Examples
GARD 8000 Distance Relay
RFL Electronics Inc.
Fault current studies should confirm this setting, taking into account the scheme used and whether
directional ground elements are applied to cover high resistance ground faults.
Description Range
Units
Step
Actual
46 Open phase enable
Enables the Broken Conductor (open phase) function
No - Yes
-
1
No
46 Open phase pick up
Pick-up setting for broken conductor function. The pick-up level
is set as I
2
/I
1
, the ratio of negative sequence and
positive sequence current.
0.05 - 0.4
I2/I1
0.01
0.05
46 Open phase time delay
Time delay for trip for broken conductor
0.05 - 300
s
0.01
0.05
46 Minimum load
Sets minimum load level for the broken conductor function.
If the positive sequence current is below this level, the broken
conductor function is blocked.
0.10 - 5
A
0.01
0.5
Forward Sup. 1-Ph
Minimum operating current for forward phase-
ground impedance zone operation
0.20 - 7.5
A
0.01
5.34
Forward Sup. 2-Ph
Minimum operating current for forward phase-
phase and three-phase impedance zone operation
0.20 - 7.5
A
0.01
5.34
Reverse Sup. 1-Ph
Minimum operating current for reverse phase-ground
impedance zone operation. When using Zone 4 reverse
looking for directional comparison blocking (DCB) pilot
schemes, the reverse sensitivity should be set higher (lower
setting of the current supervision element) than the forward
elements to ensure proper coordination.
0.20 - 7.5
A
0.01
4.90
Reverse Sup. 2-Ph
Minimum operating current for forward phase-phase and
three-phase impedance zone operation. When using Zone
4 reverse looking for directional comparison blocking (DCB)
pilot schemes, the reverse sensitivity should be set higher
(lower setting of the current supervision element) than the
forward elements to ensure proper coordination.
0.20 - 7.5
A
0.01
4.90
49 Thermal Img. Enable
Enables the thermal image function
No - Yes
-
1
No
49 Heating constant
Heating constant for the line.
0.50 - 300
min
0.01
0.50
49 Cooling constant
Cooling constant for the line.
0.50 - 300
min
0.01
0.50
49 Max. Sust. Curr.
Maximum allowed continuous load current on the line
1 - 12.5
A
0.5
5
49 Alarm Level
Thermal image alarm level
50 - 100
%
1
50
August 1, 2009
8-24
973.334.3100
Содержание GARD 8000
Страница 14: ...GARD 8000 Distance Relay RFL Electronics Inc This page intentionally left blank April 1 2010 xiv 973 334 3100...
Страница 229: ...Distance Relay Logic Programming GARD 8000 Distance Relay RFL Electronics Inc March 1 2009 11 21 973 334 3100...
Страница 231: ...Distance Relay Logic Programming GARD 8000 Distance Relay RFL Electronics Inc March 1 2009 11 23 973 334 3100...
Страница 270: ...Application Notes GARD 8000 Distance Relay RFL Electronics Inc March 1 2009 14 2 973 334 3100...