Description of Operation
GARD 8000 Distance Relay
RFL Electronics Inc.
Figure 9-59. Block Diagram for Phase Undervoltage units
9.17.2
PHASE OVERVOLTAGE UNITS (59P)
The GARD 8000 has three independent phase overvoltage units. Each can be selected to measure on
phase-ground or phase-phase voltage.
The overvoltage units measure in each phase, and the output can be selected to be from each phase
separately (OR) or for all three phases (AND). This setting selection is done independently for each of
the three units:
•
AND
: The unit trips when all three phase elements pick up
•
OR
: The unit trips when any one of the three phase elements pick-up
The three units also have independent time delay settings.
A typical example for the overvoltage units could be:
•
59P-1 set to 1.2 times nominal voltage with AND logic and instantaneous trip
•
59P-2 set to 1.1 times nominal voltage with OR logic and time delayed trip
August 1, 2009