Distance Relay Setting Examples
GARD 8000 Distance Relay
RFL Electronics Inc.
8.2.14
CURRENT ELEMENTS – GROUND ELEMENTS
This example is using instantaneous ground elements for the Fast Carrier start (21L DCB) and the 67
DCB scheme. If negative sequence elements are selected for the 67 DCB, corresponding settings
should be entered on “Current Elements – Negative Sequence Elements”.
Note that Torque Control (Directional) is applied for the 67 DCB elements. However, the 50G-1 used
in the Fast Carrier start logic is using the non-directional 50G-1 element
.
Description Range
Units
Step
Actual
Enable instantaneous ground (50G-1)
Enable instantaneous ground overcurrent element, step 1
No - Yes
-
1
Yes
50G-1 Pick-Up
Pick-up level for instantaneous ground overcurrent element, step 1
0.600 - 150
A
0.01
4.90
50G-1 Time-Delay
Time delay for instantaneous ground overcurrent element, step 1
0 - 300
s
0.01
0
50G-1 Torque Control Direction
Directional control of instantaneous ground overcurrent element,
step 1
NO
Forward
Reverse
- 1
Forward
50G-1 Torque Control Type
Selection to use directional element or Zone 2 for torque control of
the instantaneous ground overcurrent element, step 1
67G
67Q
Z2G
- 1
67G
Enable instantaneous ground (50G-2)
Enable instantaneous ground overcurrent element, step 2
No - Yes
-
1
Yes
50G-2 Pick-Up
Pick-up level for instantaneous ground overcurrent element, step 2
0.600 - 150
A
0.01
1.50
50G-2 Time-Delay
Time delay for instantaneous ground overcurrent element, step 2
0 - 300
s
0.01
0
50G-2 Torque Control Direction
Directional control of instantaneous ground overcurrent element,
step 2
NO
Forward
Reverse - 1
Forward
50G-2 Torque Control Type
Selection to use directional element or Zone 2 for torque control of
the instantaneous ground overcurrent element, step 2
67G
67Q
Z2G -
1
67G
Enable instantaneous ground (50G-3)
Enable instantaneous ground overcurrent element, step 3
No - Yes
-
1
Yes
50G-3 Pick-Up
Pick-up level for instantaneous ground overcurrent element, step 3
0.600 - 150
A
0.01
1.12
50G-3 Time-Delay
Time delay for instantaneous ground overcurrent element, step 3
0 - 300
s
0.01
0
50G-3 Torque Control Direction
Directional control of instantaneous ground overcurrent element,
step 3
NO
Forward
Reverse - 1
Reverse
50G-3 Torque Control Type
Selection to use directional element or Zone 2 for torque control of
the instantaneous ground overcurrent element, step 3
67G
67Q
Z2G -
1
67G
Enable timeovercurrent ground (51G-1)
Enable ground timeovercurrent element, step 1
No - Yes
-
1
No
51G-1 Pick-Up
Pick-up level for ground timeovercurrent element, step 1
0.600 - 125
A
0.01
1
August 1, 2009
8-34
973.334.3100
Содержание GARD 8000
Страница 14: ...GARD 8000 Distance Relay RFL Electronics Inc This page intentionally left blank April 1 2010 xiv 973 334 3100...
Страница 229: ...Distance Relay Logic Programming GARD 8000 Distance Relay RFL Electronics Inc March 1 2009 11 21 973 334 3100...
Страница 231: ...Distance Relay Logic Programming GARD 8000 Distance Relay RFL Electronics Inc March 1 2009 11 23 973 334 3100...
Страница 270: ...Application Notes GARD 8000 Distance Relay RFL Electronics Inc March 1 2009 14 2 973 334 3100...