Description of Operation
GARD 8000 Distance Relay
RFL Electronics Inc.
Carrier Receive
Forward pilot zone
Three Poles Open
Power swing block
Block pilot trip
Weak infeed trip
distance
Zone 1 Fault
100ms
0
Enable open breaker
carrier send
0
T
Dist carrier send
extend time
Enable Distance
pilot scheme
power swing block
Distance pilot
protection trip
Distance
protection channel
start
Figure 9-14. PUTT
An open circuit breaker carrier send signal selection is included in the settings, ‘Enable open breaker
carrier send’. To determine if the three poles have opened, three status contact inputs (one for each
pole) can be used, or one input can be used that corresponds to the three poles in series.
The “Dist carrier send extend time’ provides a minimum time for channel signal transmission. Channel
tripping and channel sending can be disabled using the status contact input ‘Block pilot trip’. It can
also be disabled for power swing conditions by adjusting the Power swing Element ‘Distance pilot
scheme power swing block’ setting.
In case weak infeed logic is to be used with the PUTT scheme, the setting should be ‘TRIP+ECHO’.
The ‘Echo’ setting is of no use for an underreach scheme and the ‘Trip+ECHO’ setting allows for local
trip, even though no echo function will be performed (as the sending end has already tripped from its
sending, underreach zone).
9.2.4
DIRECT TRANSFER TRIP
This scheme is similar to Permissive Underreach Transfer Trip (PUTT) with the difference that
channel signal reception produces instantaneous tripping without additional supervision. The carrier
receive signal is provided with a pick-up delay to prevent tripping for spurious carrier signals, set on
timer ‘Security Time’. Carrier send (Distance protection channel start) can be initiated by an open
breaker as selected by the setting ‘Enable open breaker carrier send’. Power swing can be set to block
carrier send by the setting ‘Distance pilot scheme power swing block’ and both trip and carrier send
are blocked by the signal input ‘Block pilot trip’.
August 1, 2009
9-18
973.334.3100
Содержание GARD 8000
Страница 14: ...GARD 8000 Distance Relay RFL Electronics Inc This page intentionally left blank April 1 2010 xiv 973 334 3100...
Страница 229: ...Distance Relay Logic Programming GARD 8000 Distance Relay RFL Electronics Inc March 1 2009 11 21 973 334 3100...
Страница 231: ...Distance Relay Logic Programming GARD 8000 Distance Relay RFL Electronics Inc March 1 2009 11 23 973 334 3100...
Страница 270: ...Application Notes GARD 8000 Distance Relay RFL Electronics Inc March 1 2009 14 2 973 334 3100...