Distance Relay Setting Examples
GARD 8000 Distance Relay
RFL Electronics Inc.
Description Range
Units
Step
Actual
51G-1 Time Curve
Sets the time/current characteristic for ground timeovercurrent
element, step 1
(see time
curve
selection
below) - 1
Definite
Time
51G-1 Time Dial
Sets the time dial for the selected curve
0.05 - 10
-
0.01
1
51G-1 Time Delay
Sets the minimum time delay for the curves with Time Limit (TL)
for the ground timeovercurrent element, step 1
0.05 - 300
A
0.01
0.05
51G-1 Torque Control Type
Selection to use directional element or Zone 2 for torque control of
the ground timeovercurrent element, step 1
67G
67Q
Z2G -
1 67N
51G-1 Torque Control Direction
Directional control of ground timeovercurrent element, step 1
NO
Forward
Reverse
- 1 NO
Enable timeovercurrent ground 51G-2)
Enable ground timeovercurrent element, step 2
No - Yes
-
1
No
51G-2 Pick-Up
Pick-up level for ground timeovercurrent element, step 2
0.600 - 125
A
0.01
1
51G-2 Time Curve
Sets the time/current characteristic for ground timeovercurrent
element, step 2
(see time
curve
selection
below) - 1
Definite
Time
51G-2 Time Dial
Sets the time dial for the selected curve
0.05 - 10
-
0.01
1
51G-2 Time Delay
Sets the minimum time delay for the curves with Time Limit (TL)
for the ground timeovercurrent element, step 2
0.05 - 300
s
0.01
0.05
51G-2 Torque Control Type
Selection to use directional element or Zone 2 for torque control of
the ground timeovercurrent element, step 2
67G
67Q
Z2G -
1 67N
51G-2 Torque Control Direction
Directional control of ground timeovercurrent element, step 2
NO
Forward
Reverse - 1 NO
Enable timeovercurrent ground (51G-3)
Enable ground timeovercurrent element, step 3
No - Yes
-
1
No
51G-3 Pick-Up
Pick-up level for ground timeovercurrent element, step 3
0.600 - 125
A
0.01
1
51G-3 Time Curve
Sets the time/current characteristic for ground timeovercurrent
element, step 3
(see time
curve
selection
below) - 1
Definite
Time
51G-3 Time Dial
Sets the time dial for the selected curve
0.05 - 10
-
0.01
1
51G-3 Time Delay
Sets the minimum time delay for the curves with Time Limit (TL)
for the ground timeovercurrent element, step 3
0.05 - 300
s
0.01
0.05
August 1, 2009
8-35
973.334.3100
Содержание GARD 8000
Страница 14: ...GARD 8000 Distance Relay RFL Electronics Inc This page intentionally left blank April 1 2010 xiv 973 334 3100...
Страница 229: ...Distance Relay Logic Programming GARD 8000 Distance Relay RFL Electronics Inc March 1 2009 11 21 973 334 3100...
Страница 231: ...Distance Relay Logic Programming GARD 8000 Distance Relay RFL Electronics Inc March 1 2009 11 23 973 334 3100...
Страница 270: ...Application Notes GARD 8000 Distance Relay RFL Electronics Inc March 1 2009 14 2 973 334 3100...