Distance Relay Settings
GARD 8000 Distance Relay
RFL Electronics Inc.
Description Range
Units
Step
Default
50Q-2 Torque control
Directional control of instantaneous negative sequence
overcurrent element, step 2
No
Forward
Reverse - 1
N0
50Q-2 Torque control type
Selection to use directional element or Zone 2 for torque control
of the instantaneous negative sequence overcurrent element,
step 2
67Q
Z2 -
1 67Q
50Q-3 Instantaneous negative sequence enable
Enable instantaneous negative sequence overcurrent element,
step 3
No - Yes
-
1
No
50Q-3 Pickup
Pickup level for instantaneous negative sequence overcurrent
element, step 3
0.25 - 150
A
0.01
10
50Q-3 Time delay
Time delay for instantaneous negative sequence overcurrent
element, step 3
0 - 300
s
0.01
0
50Q-3 Torque control
Directional control of instantaneous negative sequence
overcurrent element, step 3
No
Forward
Reverse - 1
No
50Q-3 Torque control type
Selection to use directional element or Zone 2 for torque control
of the instantaneous negative sequence overcurrent element,
step 3
67Q
Z2
- 1
67Q
51Q-1 Negative sequence timeovercurrent enable
Enable negative sequence timeovercurrent element, step 1
No - Yes
-
1
No
51Q-1 Pickup
Pickup level for negative sequence timeovercurrent element,
step 1
0.50 - 25
A
0.01
2
51Q-1 Time curve
Sets the time/current characteristic for the negative sequence
timeovercurrent element, step 1
* (see time
curve
selection
below)
- 1
Definite
Time
51Q-1 Time dial
Sets the time dial for the selected curve
0.05 - 10
-
0.01
1
51Q-1 Fixed time
Sets the minimum time delay for the curves with Time Limit
(TL) for the negative sequence timeovercurrent element, step 1
0.05 - 300
s
0.01
0.05
51Q-1 Torque control type
Selection to use directional element or Zone 2 for torque control
of the negative sequence timeovercurrent element, step 1
67Q
Z2 -
1 67Q
51Q-1 Torque control
Directional control of negative sequence timeovercurrent
element, step 1
No
Forward
Reverse - 1
No
51Q-2 Negative sequence timeovercurrent enable
Enable negative sequence timeovercurrent element, step 2
No - Yes
-
1
No
51Q-2 Pickup
Pickup level for negative sequence timeovercurrent element,
step 2
0.50 - 25
A
0.01
2
51Q-2 Time curve
Sets the time/current characteristic for the negative sequence
timeovercurrent element, step 2
* (see time
curve
selection
below)
- 1
Definite
Time
51Q-2 Time dial
Sets the time dial for the selected curve
0.05 - 10
-
0.01
1
July 21, 2009
7-21
973.334.3100
Содержание GARD 8000
Страница 14: ...GARD 8000 Distance Relay RFL Electronics Inc This page intentionally left blank April 1 2010 xiv 973 334 3100...
Страница 229: ...Distance Relay Logic Programming GARD 8000 Distance Relay RFL Electronics Inc March 1 2009 11 21 973 334 3100...
Страница 231: ...Distance Relay Logic Programming GARD 8000 Distance Relay RFL Electronics Inc March 1 2009 11 23 973 334 3100...
Страница 270: ...Application Notes GARD 8000 Distance Relay RFL Electronics Inc March 1 2009 14 2 973 334 3100...