Distance Relay Settings
GARD 8000 Distance Relay
RFL Electronics Inc.
Description Range
Units
Step
Default
Series compensation enable
Enables series compensation logic
No – Yes
-
1
No
Series compensation time delay
Drop-out delay of the series compensation transient block signal
0 – 100
s
0.01
1
Series compensation Zone 4 supervision
Determines if Zone 4 reverse element is used for the transient
block logic
No – Yes
-
1
No
Series compensation 67-G3 supervision
Determines if ground overcurrent reverse element (67G/50G-3) is
used for the transient block logic
No – Yes
-
1
No
Series compensation 67Q-3 supervision
Determines if negative sequence reverse element (67Q/50Q-3) is
used for the transient block logic
No – Yes
-
1
No
Series compensation 67P-3 supervision
Determines if phase overcurrent reverse element (67/50P-3) is
used for the transient block logic
No – Yes
-
1
No
Close Into Fault (CIFT) enable
No - Yes
-
1
No
CIFT supervision zone
Selects the distance zone used for close-into-fault (Z2 or Z3).
Zone 2
Zone 3
- 1
Zone
2
CIFT overcurrent pickup
Overcurrent threshold for Close-Into-Fault operation.
1 - 30
A
0.05
10
Z1 extension after reclosing
Selects if the ‘CIFT Sup. Zone’ is allowed to trip following
reclosing.
No - Yes
-
1
No
2nd harmonic restraint
Set the % for 2
nd
harmonic restraint following breaker closing.
0 - 50
%
1
0
Pole discordance enable
Enables pole discrepancy logic.
No - Yes
-
1
No
Pole discordance delay
Time delay for pole discrepancy trip.
0 - 50
s
0.01
2
81 Inhibit Voltage
Inhibit voltage for frequency measurements. When the voltage is
below the set threshold, all frequency elements are disabled.
2 - 150
V
1
40
81 Pickup Time
Activation time (Pickup time) set in number of half cycles. This
setting determines the number of half cycles used for measuring
the frequency before a frequency condition can be declared.
3 - 30
scycs
1
6
81 Dropout Time
De-activation time (drop-out time) set in number of cycles. This
determines the number of cycles used to determine that the
frequency has returned to a non-faulted condition. When the
frequency units have picked up but not yet tripped, there could be
a change in frequency of a short duration and this setting prevents
the units from dropping out for such a condition.
0 - 10
cycls
1
0
81M-1 Overfrequency enable
Enables overfrequency, step 1
No - Yes
-
1
No
81M-1 Overfrequency pickup
Pickup threshold for overfrequency, step 1
40 - 70
Hz
0.01
70
81M-1 Overfrequency time delay
Pickup time delay for overfrequency, step 1
0 - 300
s
0.01
0
81M-1 Dropout Time
Drop-out time delay for overfrequency, step 1
0 - 300
s
0.01
2
81M-2 Overfrequency enable
Enables overfrequency, step 2
No - Yes
-
1
No
July 21, 2009
7-13
973.334.3100
Содержание GARD 8000
Страница 14: ...GARD 8000 Distance Relay RFL Electronics Inc This page intentionally left blank April 1 2010 xiv 973 334 3100...
Страница 229: ...Distance Relay Logic Programming GARD 8000 Distance Relay RFL Electronics Inc March 1 2009 11 21 973 334 3100...
Страница 231: ...Distance Relay Logic Programming GARD 8000 Distance Relay RFL Electronics Inc March 1 2009 11 23 973 334 3100...
Страница 270: ...Application Notes GARD 8000 Distance Relay RFL Electronics Inc March 1 2009 14 2 973 334 3100...