Description of Operation
GARD 8000 Distance Relay
RFL Electronics Inc.
I
eq
Z
set
V
a
1
V
a
(Z
L
+Z
RS
)(I
eq
-I
a
1)
F
Figure 9-2. Mho Phase-Ground Characteristic (II)
Where:
Table 9-3. MHO Phase-Ground Characteristic Definitions
Z
LS
Local source positive sequence impedance
Z
L
Line positive sequence impedance
Z
RS
Remote source positive sequence impedance
Z
set
Set reach
I
eq
Equivalent ground fault current = I
phase
+ I
0
(K0-1)
I
a
Phase A current. The same measurement is being made for
phase B and C.
I1
Positive sequence fault current
V
a
Phase A voltage. The same measurement is being made for
phase B and C.
V1
Polarizing voltage. Positive sequence voltage, referenced to the
faulted phase.
August 1, 2009
9-4