Distance Relay Setting Examples
GARD 8000 Distance Relay
RFL Electronics Inc.
8.2.13
CURRENT ELEMENTS – PHASE ELEMENTS
In this example, only 50-P1 for the Fast Carrier start is of interest for the application.
Description Range
Units
Step
Actual
Enable instantaneous phase (50P-1)
Enable instantaneous phase overcurrent element, step 1
No - Yes
-
1
Yes
50P-1 Pick-Up
Pick-up level for instantaneous phase overcurrent element, step 1
0.05 - 150
A
0.01
4.90
50P-1 Time-Delay
Time delay for instantaneous phase overcurrent element, step 1
0 - 300
s
0.01
0
50P-1 Torque Control Direction
Directional control of instantaneous phase overcurrent element,
step 1
NO
Forward
Reverse - 1
NO
50P-1 Torque Control Type
Selection to use directional element or Zone 2 for torque control
of the instantaneous phase overcurrent element, step 1
67P
Z2 -
1 67P
Enable instantaneous phase (50P-2)
Enable instantaneous phase overcurrent element, step 2
No - Yes
-
1
No
50P-2 Pick-Up
Pick-up level for instantaneous phase overcurrent element, step 2
0.05 - 150
A
0.01
5
50P-2 Time-Delay
Time delay for instantaneous phase overcurrent element, step 2
0 - 300
s
0.01
0
50P-2 Torque Control Direction
Directional control of instantaneous phase overcurrent element,
step 2
NO
Forward
Reverse
- 1
NO
50P-2 Torque Control Type
Selection to use directional element or Zone 2 for torque control
of the instantaneous phase overcurrent element, step 2
67P
Z2
- 1
67P
Enable instantaneous phase (50P-3)
Enable instantaneous phase overcurrent element, step 3
No - Yes
-
1
No
50P-3 Pick-Up
Pick-up level for instantaneous phase overcurrent element, step 3
0.05 - 150
A
0.01
5
50P-3 Time-Delay
Time delay for instantaneous phase overcurrent element, step 3
0 - 300
s
0.01
0
50P-3 Torque Control Direction
Directional control of instantaneous phase overcurrent element,
step 3
NO
Forward
Reverse - 1
NO
50P-3 Torque Control Type
Selection to use directional element or Zone 2 for torque control
of the instantaneous phase overcurrent element, step 3
67P
Z2 -
1 67P
Enable timeovercurrent phase (51P-1)
Enable phase timeovercurrent element, step 1
No - Yes
-
1
No
51P-1 Pick-Up
Pick-up level for phase timeovercurrent element, step 1
0.10 - 125
A
0.01
2
51P-1 Time Curve
Sets the time/current characteristic for phase timeovercurrent
element, step 1
(see time
curve
selection
below) - 1
Definite
Time
August 1, 2009
8-32
973.334.3100
Содержание GARD 8000
Страница 14: ...GARD 8000 Distance Relay RFL Electronics Inc This page intentionally left blank April 1 2010 xiv 973 334 3100...
Страница 229: ...Distance Relay Logic Programming GARD 8000 Distance Relay RFL Electronics Inc March 1 2009 11 21 973 334 3100...
Страница 231: ...Distance Relay Logic Programming GARD 8000 Distance Relay RFL Electronics Inc March 1 2009 11 23 973 334 3100...
Страница 270: ...Application Notes GARD 8000 Distance Relay RFL Electronics Inc March 1 2009 14 2 973 334 3100...