Commissioning
GARD 8000 Distance Relay
RFL Electronics Inc.
6.
All Voltage and Current levels should be zero if the external current and voltage sources are not
applied.
7.
Connect a Power System Simulator, apply current or voltage, refresh the screen and verify the
metering values.
12.9
INPUT/OUTPUT MAPPING VERIFICATION
•
The physical Inputs and Outputs are mapped on the “System Logic Configuration” web page.
Any available hardware input or output can be freely assigned to any logical input or output
that is available in the Input or Output mapping block (please use the GARD logic drawing as a
reference). Verify which current logical inputs and outputs are mapped to the hardware inputs
and outputs using the web pages. Additional logical inputs or outputs could be mapped in the
Input Mapping and Output Mapping Logic blocks located in the Distance Relay Logic Design.
1.
At the “Home” web page click on “Settings” and select “System Logic Configuration.”
2.
Click on “Input Mapping” and verify all Input Mapping.
March 1, 2009
12-7
973.334.3100
Содержание GARD 8000
Страница 14: ...GARD 8000 Distance Relay RFL Electronics Inc This page intentionally left blank April 1 2010 xiv 973 334 3100...
Страница 229: ...Distance Relay Logic Programming GARD 8000 Distance Relay RFL Electronics Inc March 1 2009 11 21 973 334 3100...
Страница 231: ...Distance Relay Logic Programming GARD 8000 Distance Relay RFL Electronics Inc March 1 2009 11 23 973 334 3100...
Страница 270: ...Application Notes GARD 8000 Distance Relay RFL Electronics Inc March 1 2009 14 2 973 334 3100...