Distance Relay Setting Examples
GARD 8000 Distance Relay
RFL Electronics Inc.
Description Range
Units
Step
Actual
Zone 3 Enable
Enable operation of Zone 3 distance
No – Yes
-
1
Yes
Zone 3 direction
Zone 3 measuring direction, forward or reverse.
Reverse
Forward
- 1
Forward
Zone 3 reach
Zone 3 reactive reach in secondary ohms, at set characteristic line
angle.
0.01 – 100
Ohm
0.01
8.26
1-Ph Resistive Limit Zone 3
Resistive reach in secondary ohms for Zone 3 phase-ground
quadrilateral characteristic. Note that the set resistance is the direct
loop resistance, without zero sequence compensation factor
applied. For phase A, the resistance at the R-axis is R
set
= V
A
/I
A
.
0.01 – 100
-
0.01
4
2-Ph Resistive Limit Zone 3
Resistive reach in secondary ohms for Zone 3 phase-phase
quadrilateral characteristic. Note that the set resistance is the
phase-phase resistance. For phase A to B, the resistance at the R-
axis is R
set
= V
AB
/I
AB
.
0.01 - 100
-
0.01
4
Zone 3 ground timer
Zone 3 ground elements time delay
0 - 300
s
0.01
0.8
Zone 3 phase timer
Zone 3 phase elements time delay
0 - 300
s
0.01
0.8
Zone 4 Enable
Enable operation of Zone 4 distance
No – Yes
-
1
Yes
Zone 4 direction
Zone 4 measuring direction, forward or reverse. Note that when
the pilot logic “Directional Comparison Blocking’, “Weak Infeed”
and/or ‘Transient Block” is used, Zone 4 is always reverse,
regardless of this setting.
Reverse
Forward
- 1
Reverse
Zone 4 reach
Zone 4 reactive reach in secondary ohms, at set characteristic line
angle.
0.01 - 100
Ohm
0.01
2.07
1-Ph Resistive Limit Zone 4
Resistive reach in secondary ohms for Zone 4 phase-ground
quadrilateral characteristic. Note that the set resistance is the direct
loop resistance, without zero sequence compensation factor
applied. For phase A, the resistance at the R-axis is R
set
= V
A
/I
A
.
0.01 - 100
-
0.01
4
2-Ph Resistive Limit Zone 4
Resistive reach in secondary ohms for Zone 3 phase-phase
quadrilateral characteristic. Note that the set resistance is the
phase-phase resistance. For phase A to B, the resistance at the R-
axis is R
set
= V
AB
/I
AB
.
0.01 - 100
-
0.01
4
Zone 4 ground timer
Zone 4 ground elements time delay
0 - 300
s
0.01
1.5
Zone 4 phase timer
Zone 4 phase elements time delay
0 - 300
s
0.01
1.5
August 1, 2009
8-10
973.334.3100
Содержание GARD 8000
Страница 14: ...GARD 8000 Distance Relay RFL Electronics Inc This page intentionally left blank April 1 2010 xiv 973 334 3100...
Страница 229: ...Distance Relay Logic Programming GARD 8000 Distance Relay RFL Electronics Inc March 1 2009 11 21 973 334 3100...
Страница 231: ...Distance Relay Logic Programming GARD 8000 Distance Relay RFL Electronics Inc March 1 2009 11 23 973 334 3100...
Страница 270: ...Application Notes GARD 8000 Distance Relay RFL Electronics Inc March 1 2009 14 2 973 334 3100...