4.6 Combustion Fan Assembly
Induced Burner
STEP 1
Loosen the clamp fitting on the flue and
remove.
STEP 2
Loosen the 4mm grub screw.
The combustion fan can now be detached.
STEP 3
Remove the fan orifice plate spinning.
STEP 3
Inspect the impeller and ensure it rotates freely.
Remove any dust from the impeller, fan scroll
and around the motor with a soft brush.
Refit components.
4.7 Radiant Tube Servicing
STEP 1
Brush any dust from the exterior of the tubes.
Inspect the tubes visually. If the tubes appear
clean, skip to servicing the reflector.
Remove the U bend (or damper - HB products
or condensate box - DLE products)
4.8 Reflector Servicing
The condition of the reflectors should be noted. If necessary the reflectors can be cleaned
with a mild detergent. This can significantly improve the efficiency of the appliance.
Inspection of Flue
The flue needs to be inspected and cleaned
if necessary or in accordance to the regu-
lations of the country that the appliance
is installed.
Re-commissioning After Service
After servicing the heater has been under-
taken, it will be necessary to re-commission
the heater as detailed in Section 3 of these
instructions.
STEP 2
Withdraw the turbulators from the appliance.
Carefully noting their condition and position.
Replace turbulators if necessary.
The turbulators should be cleaned with a soft
brush.
If required the interior of the tubes can then be
cleaned using an industrial vacuum cleaner or
by using long poles and a scraper.
Refit components
49
Содержание VS15LHE8
Страница 34: ...A Figure 41 Vision Heater Assembly Models VSUTE VSUHE 15kW 76mm 3ins Nom Dia 34...
Страница 35: ...A A Figure 42 Vision Heater Assembly Models VSUTE VSUHE 20 25kW 76mm 3ins Nom Dia 35...
Страница 36: ...Figure 43 Vision Heater Assembly Models VSUTE VSUHE 30 35kW 100mm 4ins Nom Dia 36...
Страница 37: ...Figure 44 Vision Heater Assembly Models VSUTE VSUHE 40kW 100mm 4ins Nom Dia 37...
Страница 38: ...Figure 45 Vision Heater Assembly Models VSUTE VSUHE 45 50kW 100mm 4ins Nom Dia 38...
Страница 39: ...A Figure 46 Vision Heater Assembly Models VSLIE VSLHE VSDLE 15 25kW 8m 76mm 3ins Nom Dia 39...
Страница 40: ...A Figure 47 Vision Heater Assembly Models VSLIE VSLHE VSDLE 20 25kW 10 5m 76mm 3ins Nom Dia 40...
Страница 41: ...Figure 48 Vision Heater Assembly Models VSLIE VSLHE VSDLE 30 35kW 10 5m 100mm 4ins Nom Dia 41...
Страница 42: ...Figure 49 Vision Heater Assembly Models VSLIE VSLHE VSDLE 30 35 40 45 50kW 13 5m 100mm 4in Nom Dia 42...
Страница 43: ...Figure 50 Vision Heater Assy Models VSLIE VSLHE VSDLE 35 40 45 50 kW 16m 100mm 4ins Nom Dia 43...