4:3
To initialize the regulator, do the
following:
1.
Uncouple the motor from the
load.
2.
Determine which initialization
(INIT0, INIT2, or INIT3) and
procedure to use based on the
motor’s pole/RPM and
encoder characteristics.
Refer to Table 4-1.
3.
(INIT0)
– Use this step for 4
pole motors only.
3.1 Turn power OFF.
3.2 Set 1SW DIP switches for
INIT0 as shown in
Figure 4-1.
Figure 4-1. INIT0 1SW DIP Switch Settings.
3.3 Turn power ON for 10
seconds.
3.4 Turn power OFF. INIT0
procedure is now
complete.
3.5 Refer to Table 3-4 to set
1SW switches per your
application requirements.
3.6 Continue with the startup
and adjustment
instructions for “Review
the Controller Regulator
Jumpers” in this section.
4.
(INIT2)
– Use this step for 8
pole motors only .
4.1 Turn power OFF.
4.2 Set 1SW DIP switches for
INIT2 as shown in
Figure 4-2.
4.3 Turn power ON for 10
seconds.