411
3. Verify that jumper J8 is properly positioned for your reference signal.
4. Apply AC input power and then press the Start button.
WARNING
ADJUSTMENT OF THE PROCESS INTERFACE BIAS POTENTIOMETER
COULD RESULT IN ZERO SPEED OPERATION OF THE CONTROLLER. THE
DRIVE IS INTENDED TO OPERATE AT A PREDETERMINED MINIMUM SPEED
UNLESS DISCONNECTED FROM THE POWER SOURCE. IF THE APPLICA
TION REQUIRES ZERO SPEED OPERATION WITHOUT SUCH DISCONNEC
TION, THE USER IS RESPONSIBLE FOR ASSURING SAFE CONDITIONS FOR
OPERATING PERSONNEL BY PROVIDING SUITABLE GUARDS, AUDIBLE OR
VISUAL ALARMS, OR OTHER DEVICES. FAILURE TO OBSERVE THIS PRE
CAUTION COULD RESULT IN BODILY INJURY.
5. Command minimum reference from your process control unit and
adjust PI BIAS to the desired minimum operating speed or torque.
6. Increase the process control reference signal to maximum and
adjust PI GAIN to the desired maximum operating speed or torque.
It may be necessary to repeat Steps 5 and 6 until proper maximum
and minimum speed or torque are attained because these
adjustments interact.
7. Press the Stop switch and wait for the motor to completely stop.
Adjust Rate Potentiometer(s)
With Speed Control models:
Adjust RATE 1 and RATE 2 for desired acceleration and deceleration
rates.
With Torque Control models:
1. Set J401 for Fast or Slow rate range:
NOTE:
F (Fast) setting is used for finer resolution at faster rates.
S(Slow) - 3.5 to 40 seconds
F(Fast) - 0.3 to 3.5 seconds
2. Adjust RATE 1 for the desired acceleration rate.
3. Adjust RATE 2 for the desired deceleration rate.
Содержание DC2 VS series
Страница 1: ......
Страница 2: ......
Страница 3: ......
Страница 4: ......
Страница 5: ......
Страница 31: ...3 16 419 519 TB2 Motor Mounted D C Tachometer Figure 3 8 D C Tachometer Connection...
Страница 48: ...5 6 Figure 5 1 Wiring Diagram of Basic Speed Controller 0 57210 30...
Страница 49: ...5 7...
Страница 51: ...5 9 J4...
Страница 53: ...5 11 DEVICE INTERCONNECTIONS BACK OF REVERSING SWITCH Figure 5 3 Operator Device Interconnections...
Страница 56: ...Reliance Electric 24701 Euclid Avenue Cleveland Ohio 44117 216 266 7000 Printed in U S A D2 3231 3 March 1994...