38
Wire the Drive
DANGER
THE USER IS RESPONSIBLE FOR CONFORMING TO THE NATIONAL ELEC
TRICAL CODE AND ALL OTHER APPLICABLE LOCAL CODES. WIRING
PRACTICES, GROUNDING, DISCONNECTS AND OVERCURRENT PROTEC
TIONS ARE OF PARTICULAR IMPORTANCE. FAILURE TO OBSERVE THESE
PRECAUTIONS COULD RESULT IN SEVERE BODILY INJURY OR LOSS OF
LIFE.
DANGER
THIS EQUIPMENT IS AT LINE VOLTAGE WHEN AC POWER IS CONNECTED.
DISCONNECT AND LOCKOUT ALL UNGROUNDED CONDUCTORS OF THE A
C POWER LINE. FAILURE TO OBSERVE THESE PRECAUTIONS COULD RE
SULT IN SEVERE BODILY INJURY OR LOSS OF LIFE.
NOTE:
All remote operation wiring should be no longer than 250 feet.
Ground the Controller and Enclosure, the Motor
and the Operator's Control Station.
DANGER
CONNECT THE GROUND WIRE BROUGHT IN WITH THE INCOMING AC
POWER LINE TO THE CONTROLLER GROUND POINT. CONNECT AN APPRO
PRIATE EQUIPMENT GROUNDING CONDUCTOR UNBROKEN FROM THE
CONTROLLER GROUND POINT, THE MOTOR FRAME, THE TRANSFORMER
ENCLOSURE IF USED, THE CONTROLLER ELECTRICAL ENCLOSURE, THE
WIRING CONDUITS, AND THE OPERATOR'S CONTROL STATION TO AN AP
PROPRIATE GROUNDING ELECTRODE. FAILURE TO OBSERVE THIS PRE
CAUTION COULD RESULT IN SEVERE BODILY INJURY OR LOSS OF LIFE.
1. Locate the convienence ground point provided at the bottom edge
of the heat sink.
2. Run a suitable equipment grounding conductor
unbroken
from this
controller ground point to the plant ground (grounding electrode). A
ring lug is recommended at the ground point.
3. Connect a suitable grounding conductor from each conduit to this
controller ground point.
4. Connect a suitable equipment grounding conductor to the motor
frame, the transformer enclosure if used, and the controller
enclosure. Run this conductor
unbroken
to the grounding
electrode.
5. Connect the ground wire brought in with the incoming AC power
line to the controller ground point.
Содержание DC2 VS series
Страница 1: ......
Страница 2: ......
Страница 3: ......
Страница 4: ......
Страница 5: ......
Страница 31: ...3 16 419 519 TB2 Motor Mounted D C Tachometer Figure 3 8 D C Tachometer Connection...
Страница 48: ...5 6 Figure 5 1 Wiring Diagram of Basic Speed Controller 0 57210 30...
Страница 49: ...5 7...
Страница 51: ...5 9 J4...
Страница 53: ...5 11 DEVICE INTERCONNECTIONS BACK OF REVERSING SWITCH Figure 5 3 Operator Device Interconnections...
Страница 56: ...Reliance Electric 24701 Euclid Avenue Cleveland Ohio 44117 216 266 7000 Printed in U S A D2 3231 3 March 1994...