Regency GF1500LST Gas Fireplace
23
installation
Horizontal Venting with Two (2) 90
o
Elbows
Notes:
1. Liner sections should be continuous without any joints or
seams.
2. Only Flex pipe purchased from FPI may be used for Flex
installations.
3. Horizontal flue must be supported every 0.9 m.
4. A wall thimble is mandatory for all horizontal terminations
due to high temperatures.
H
H1
V
One 90
o
elbow = Two 45
o
elbows.
Option
V
H + H1
With these options, maximum
total pipe length is 4.5m with
minimum of 1.5m of vertical.
Please note min. 0.3m
between 90
o
elbows is
required.
A)
0.6m min.
0.6m max.
B)
0.9m min.
1.2m max.
C)
1.2m min.
1.8m max.
D)
1.5m min.
3.0m max.
Lengths do not include
elbow indicated.
Restrictor Set 0
Factory set - fully open