background image

26

Regency GF1500LST Gas Fireplace

installation

Diagram 4

Diagram 3

7.  Ensure that  the pipe  clearances  to  com-

bustible materials are maintained (Diagram 
3). Install the termination cap.

 

The four wood screws provided should be re-
placed with appropriate fasteners for stucco, 
brick, concrete, or other types of sidings.

8.  Before  connecting  the horizontal run of flue 

pipe to the vent termination, slide the Wall 
Thimble  over the vent pipe. The wall thimble 
is required for all horizontal terminations.

9.  Slide the appliance and flue assembly towards 

the wall carefully inserting the flue pipe into 
the flue cap assembly. It is important that the 
flue pipe  extends  into the flue cap sufficient 
distance so as to result in a minimum pipe 
overlap  of  32mm.  Secure  the  connection 
between the flue pipe and the flue  cap.

10. Install wall thimble in the center of the  279mm 

square and attach with wood screws (Diagram 
4).

UNIT INSTALLATION WITH 
HORIZONTAL TERMINATION

(Rigid Flue Systems)

A top clearance of 76mm and side & bottom 
clearance of  51mm must be maintained; except 
when passing  through  a  wall, ceiling, or  at  
the  termination where the use of a wall thimble 
reduces the required clearance to 38mm. We 
recommend framing a 279mm x 279mm (inside 
dimensions) hole to give structural rigidity for 
mounting the termination.

Install    the  flue    system  according  to  the 
manufacturer's  instructions  included  with  the 
components.

1.  Set the unit in its desired location. Check to 

determine  if  wall  studs  or  roof  rafters  are  in 
the way when the flueing system is attached. 
If this is the case, you may want to adjust the 
location of the unit. Rough in the gas preferably 
on the right side of the unit.

2.  Simpson Dura-Vent Flue pipe and fittings are 

designed with special twist-lock connections to 
connect the venting system to the appliance 
flue  outlet.  A  twist-lock  appliance  adaptor  is 
required.

Note:   If using Flomet Rigid Flue System (Part 

No:  946-686), no Twist-lock appliance 

adaptor is required.

3.  In  conjunction  with  the  Simpson  Direct Vent 

Pro system, install the adaptor after the unit 
is set in its desired location. Put a bead of Mill 
Pac inside the outer section of the adapter and 
a bead of Mill Pac on the inner collar. Slip the 
adapter over the existing inner and outer flue 
collar. Fasten to the outer collar only with the 
3 supplied screws (drilling pilot holes will make 
this easier).

4.  Level the fireplace and fasten it to the framing 

using nails or screws through the top and side 
nailing strips.

5.  Assemble the desired combination of pipe and 

elbows    to    the    appliance    flue  outlets  and 
secure.

Note:   For  best  results  and  optimum 

performance      with      each  approved 

flueing  system, apply “Mill-Pac” sealant  

to every  inner  pipe  connection. Failure  

to  do  so  may  result  in  drafting  or 

performance issues not covered under 

warranty. 

If Simpson Duravent Pipe Used

Diagram 1

6.  Mark the wall for a 279mm x 279mm  square 

hole. The  center of the square hole should 
line up with the center-line of the horizontal 
pipe. Cut and frame the 279mm square hole 
in  the  exterior  wall  where  the  flue  will  be 
terminated.  See  diagram  2  for  center  line 
requirements.

 

If the wall being penetrated is constructed 
of  non-combustible  material,  i.e.  masonry 
block or concrete, a 203mm diameter  hole 
is acceptable.

Diagram 2

Note:

  a)

  The horizontal run of flue must be level, or 

have a 6mm rise for every  305mm of run 

towards the termination. Never allow the 

flue to run downward. This could cause 

high temperatures and may present the 

possibility of a fire. 

 

b)

  The location of the horizontal flue  

termination on an exterior wall must meet 

all local and national building codes, and 

must not be blocked or obstructed.  See 

"Exterior  Flue  Termination  Locations" 

section for more details.

Horizontal  runs  of  flue  must  be  supported 

every 0.9 metre. Wall straps are available for 

this purpose.

"THIS UNIT MUST ALWAYS 

TERMINATE / FLUE 

DIRECTLY TO THE 

OUTDOORS."

CL

CL

Min.  height

(Rigid)

   (1423mm)

center

of hole

NOTE: 

"NOT INTENDED FOR  

FIREPLACE INSERT". 

Содержание GF1500LST-LP

Страница 1: ... a neighbour s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department 919 670 Greenfire GF1500LST Gas Fireplace December 8 2016 Owners Installation Manual www regency fire com au Installer Please complete the details on the back cover and leave this manual with the homeowner Homeowner Please keep these instructions for future reference MODELS GF...

Страница 2: ...0 seconds To match the control box to the remote the following steps are to be followed 1 Remove a battery from the remote handset 2 Remove main power to the control box by turning off the isolation switch or switch off the GPO to the heater 3 Wait 30 seconds approx 4 Reconnect main power to the control box 5 Immediately put the battery back in the remote and point hte remote in the general direct...

Страница 3: ...lowable Vertical Terminations 25 Unit Installation with Horizontal Termination 26 Unit Installation with Vertical Termination 27 Unit Installation 28 High Elevation 29 Gas Line Installation 29 Pilot Adjustment 29 Gas Pipe Pressure Testing 29 Wiring Diagram 30 845 S I T Valve Description 30 Aeration Adjustment 30 Conversion Kit from NG to LP ULPG 31 Optional fan ducting kit installation 33 Log Set ...

Страница 4: ... NEAR THIS APPLIANCE DO NOT 908 602a Part 919 671 Serial sequence start 446000001 Colour Black on Grey Size 100 7 W x 2 7 H June 2 16 Created Decal Oct 3 16 Updated data added approval Oct 19 16 Added Min supply pressure Serial Number Regency Gas Fireplace 446 Distributed by Western Australia Air Group Australia 28 Division St Welshpool WA 6106 Eastern Australia Fireplace Products Australia Pty Lt...

Страница 5: ...2mm 39mm 39mm 1005mm 241mm 699mm 516mm 325mm 258mm 1267mm SIDE A SIDE A SIDE B SIDE B Dimension drawings shown without fascias SIDE A NOTE DUE TO NATURE AND DESIGN OF THE GF1500LST DOUBLE SIDED UNIT SIDE A PROJECTS MORE HEAT THAN SIDE B ON THE UNIT PLEASE NOTE THIS BEFORE COMMENCING THE INSTALLATION PROCESS ...

Страница 6: ...INATE FLUE DIRECTLY TO THE OUTDOORS IMPORTANT MESSAGE SAVE THESE INSTRUCTIONS The GF1500LST Direct Vent Fireplace must be installedinaccordancewiththeseinstructions Carefully read all the instructions in this manual first Consult the authority having jurisdiction to determine the need for a permit prior to starting the installation It is the responsibility of the installer to ensure this fireplace...

Страница 7: ...AssemblyPriortoInstallation 3 Slide unit into place 4 Install flue Refer to Flue Arrangement sections 5 Make gas connections Refer to Gas Line Installation section 6 Pair up Remote Control Refer to Pairing up Remote Handset section 7 Test the pilot Refer to Pilot Adjustment section 8 Test Gas Pressure Refer to Gas Pipe Pres sure Testing section 9 Install standard and optional features Refer to the...

Страница 8: ...nsion Measured From A Mantel Height min 330 mm Top of Fireplace Opening B Sidewall on one side 203 mm Side of Fireplace Opening C Ceiling min room and or alcove 1162 mm Top of Fireplace Opening D Mantel Depth max 305mm 730mm Above Fireplace Opening E Alcove Width 1676 mm Sidewall to Sidewall Minimum F Alcove Depth 914 mm Front to Back Wall Maximum G From Floor min 702 mm Top of Fireplace Opening N...

Страница 9: ...quality or the paint may discolour MANTEL LEG CLEARANCES Combustible mantel leg clearances as per diagram 203mm 146mm 219mm 295mm 178mm 102mm 203mm 178mm 178mm 102mm 146mm 219mm 295mm 330mm Top of Fireplace Opening 0 To Unit Base 22 702mm 330 Combustible Material 0 Top of Fireplace Opening Standoff Combustible Stud On Edge 0 Non combustible Facing 25mm 330mm 0 Top of Fireplace Opening 305mm 0 To U...

Страница 10: ... be adjusted back up to 38mm to allow for varying thicknesses in non combustible material wall finishes Nailing Strips DO NOT REMOVE NAILING STRIPS INSTALLATION ACCESS PANEL The unit is equipped with a removable access panel for pre finish installa tion of optional components This panel is located on the lower front face of Side B only 1 Remove 8 screws to remove access panel 2 Easier access to ga...

Страница 11: ...ming depth measurement is noted with nailing strips top sides set as far forward on the firebox as possible The nailing strips can be adjusted back up to 38mm on both sides to allow for varying thicknesses in non combustible material and wall finishes Finished material thickness includes non combustible material tile slate etc A minimum thickness of 12mm non combustible facing board compliant with...

Страница 12: ...516mm minus the overall non combustible finishing material Example 51mm of finishing material per side 414mm framing width 1 Assemble the 2 two vertical ends V of the framing kit by securing hori zontal studs H with 4 four screws securing each stud two on each side The horizontal studs H are adjustable in 12mm increments to accommo date finishing materials determine the thickness of the finishing ...

Страница 13: ...l 2 two wide studs above and below the unit as shown with 2 two screws on each side repeat on opposite side 5 Install 1 one thin vertical studs on the left side of the unit as shown with 2 two screws on each end Side Support Thin Vertical Stud 6 Completed framing kit Wide Studs Top Bottom 7 Proceed with the installation of non combustible and finishing materials ...

Страница 14: ...herefore the units are specified with non combustible required materials to specific dimensions above and around the units This is due to these areas reaching higher temperature levels than required acceptable for a combustible material To obtain the best most durable finish around your fireplace this calls for a high level of care and attention to the preparation and finish around this appliance ...

Страница 15: ... doors poor flame package carbon blue flames etc These are not product related issues 3 The unit does not have to be completely enclosed in a chase You must maintain clearances from the flue to combustible materials See Clearances section Combustible materials can be laid against the side and back standoffs and the stove base 4 Non combustible material ie tile slate etc may be brought up to and ov...

Страница 16: ... metal or concrete floor In a raised application e g on wall the appli ance must be installed on a sturdy metal wood or concrete surface extending the full width and depth of the appliance Note A minimum thickness of 12mm non combustible facing is required above the opening of the unit Note The siding nailing strips are factory set at 12 mm The top nailing strip is fixed during transit to the rear...

Страница 17: ...egency GF1500LST Gas Fireplace 17 installation EXTERIOR FLUE TERMINATION LOCATIONS FIGURE 6 2 in part LOCATION OF FLUE TERMINALS OF BALANCED FLUE AS NZ 5601 ROOM SEALED FAN ASSISTED OR OUTDOOR APPLIANCE ...

Страница 18: ...liances over 250MJ h input 1500 1500 All fan assisted flue appliances in the direction of discharge 1500 k From a mechanical air inlet including a spa blower 1500 1000 n Vertically below an openable window non mechanical air inlet or any other opening into a building iwth the exception of sub floor ventilation Space heaters up to 50MJ h input 150 150 Other appliances up to 50 MJ h input 500 500 Ap...

Страница 19: ...nd panels see instructions in this manual 2 Remove 10 screws 4 from either side 2 on the left side facing unit to remove heat baffle to access restrictor plate 3 Remove the screws that hold the flue restrictor in place 4 Adjust the flue restrictor plate to the required flue restrictor position as per the diagrams shown below 5 Once the flue restrictor plate is in the required position secure with ...

Страница 20: ...127mm flexible inner liner Kit length 3 spring spacers 4 thimble 5 AstroCap termination cap 6 screws 7 tube of Mill Pac 8 plated screws 9 S S screws 8 x 38mm drill point 946 616 3 m FLUEING ARRANGEMENTS HORIZONTAL TERMINATION FLEX Regency Direct Vent System These flueing systems in combination with GF1500LST have been tested and listed as a DirectVent system by IAPMO R T Oceana The location of the...

Страница 21: ... NZS 5601 to be supplied by installer Wallthickness ismeasuredfromthebackstandoffs to the inside mounting surface of termination cap For siding other than vinyl furring strips may be used instead of the vinyl siding standoff to create a level surface to mount the vent terminal The Terminal must not be recessed into wall cladding Measurethewallthicknessincludingwallcladding WARNING Do not combine f...

Страница 22: ...lue systems are prohibited FLUEING ARRANGEMENT FOR HORIZONTAL TERMINATIONS The diagram shows all allowable combinations of vertical runs with horizontal terminations using one 90o two 45o elbows equal one 90o elbow Note Must use optional rigid pipe adapter Part 770 994 when using Simpson DuraVent Only Maintain clearances to combustibles as listed in Clearances section Horizontal flue must be suppo...

Страница 23: ...e supported every 0 9 m 4 A wall thimble is mandatory for all horizontal terminations due to high temperatures H H1 V One 90o elbow Two 45o elbows Option V H H1 With these options maximum total pipe length is 4 5m with minimum of 1 5m of vertical Please note min 0 3m between 90o elbows is required A 0 6m min 0 6m max B 0 9m min 1 2m max C 1 2m min 1 8m max D 1 5m min 3 0m max Lengths do not includ...

Страница 24: ...erial ensure all joints outside are sealed with appropriate sealer Please note bracing appropriate flashing and heater seal not supplied 6 Fit approved gas cowl ensuring inner and outer flue pipes are sealed 7 Start heater and run for at least 15 minutes to check flue seal If operational issues are noted check flue again to ensure proper seal of inner pipe SUPPLIED Mill Pac SEALANT MUST BE USED OR...

Страница 25: ...m 1423mm Max 3m centerline to centerline Maximum 6 7m 0 6 5 6 7 7 3 Vertical Height Metres Horizontal Metres 0 1 5 Vent Restrictor on Set 3 25mm Vent Restrictor on Set 2 35mm 4 4 5 3 5 2 VENTING ARRANGEMENTS ALLOWABLE VERTICAL TERMINATIONS The shaded area in the diagram shows all allowable combinations of straight vertical and offset to vertical terminations using two 90o elbows with Rigid PipeVen...

Страница 26: ...gid Flue System Part No 946 686 no Twist lock appliance adaptor is required 3 In conjunction with the Simpson Direct Vent Pro system install the adaptor after the unit is set in its desired location Put a bead of Mill Pac inside the outer section of the adapter and a bead of Mill Pac on the inner collar Slip the adapter over the existing inner and outer flue collar Fasten to the outer collar only ...

Страница 27: ...o the position of the applianceflueexit andmark the location where the flue will penetrate the ceiling Drillasmallholeathispoint Next dropaplumbbobfrom the roof to the hole previ ously drilled in the ceiling andmarkthespotwherethe flue will penetrate the roof Determine if ceiling joists roof rafters or other fram ing will obstruct the flueing system You may wish to relocate the appliance or to off...

Страница 28: ... a wall thimble reduces the required clearance to 38mm We recommend framing a 279mm x 279mm inside dimensions hole to give structural rigidity for mountingthetermination 1 Locate the unit in the framing rough in the gas preferably on the right side of the unit Locate the centerline of the termination and mark wall accordingly Cut an 279mm hole in the wall inside dimension 2 Levelthefireplaceandfas...

Страница 29: ...nion so that gas lines can be easily disconnected for servicing Flare nuts for copper lines and flex connectors are usually considered to meet this requirement NOTE A approved shutoff valve should be supplied in or near the unit or as per local codes for ease of servicing this appliance GF1500LST NG SYSTEM DATA Min Supply Pressure 1 13 kpa Low Setting Man Pressure 0 4kpa Max Manifold Pressure 0 87...

Страница 30: ...Pilot Outlet 9 Main Gas Outlet WIRING DIAGRAM CAUTION Labelallwirespriortodisconnection when servicing controls Wiring errors can cause improper and dangerous operation Caution Ensure that the wires do not touch any hot surfaces and are away from sharp edges DISCONNECTPOWERSUPPLYTOUNITPRIOR TOWORKINGONELECTRICALCOMPONENTS SIT 201 IGNITION MODULE SIGMA 845 GND GND JUMPER 2 12 1 10 11 9 RED BLUE GRE...

Страница 31: ...o LP 1 908 528 Red Propane Label 1 918 272 Conversion to ULPG decal 1 904 529 5 32 Allen Key 1 910 101 Injector Orifice LP 35 1 919 727 Red ULPG label 1 919 728 Orange Propane label 1 919 722 Instruction Sheet Diagram 3 Remove Pilot Cap Diagram 4 Remove Pilot Orifice Diagram 5 Remove Burner Orifice Pilot Cap Pilot Orifice 6 Pull off the pilot cap to expose the pilot orifice see below 7 Unscrew the p...

Страница 32: ...d in place with velcro NOTE The maximum outlet pressure must be set to 2 49 kPa Minimum pressure Remove one of the orange wires connected to the electric modulator While holding the nut B with a spanner screw in the screw C to increase the pressure and screw it out to decrease it Orange wire Electric Modulator Jumper Location 12 Remove the jumper NOTE The minimum outlet pressure must be set to 1 6...

Страница 33: ... cause a fire hazard 6 Plan the location of the fireplace and the warm air duct runs see diagram 1 as a guide for possible duct runs and locations Diagram 1 Guide for possible air duct runs and locations Keep duct length and number of bends to a miniumum Maximum duct length is 9 0m The Extension Kit contains a maximum of up to 4 5m Please purchase the Fan Duct Extension Kit to increase the 9 0m MI...

Страница 34: ...r to the Fan Housing See diagram 4 8 Remove the knock out on the top of the unit and then remove the second knockout 9 On the top of the unit bend the 3 tabs up Insert the Duct collar Secure the collar to the 3 tabs with screws 10 You are now ready to attach fan duct to the unit Slide the ducting over the collar and secure with screws 11 Final step is to double check the fan ducting connections at...

Страница 35: ...t the wires do not touch any hot surfaces and are away from sharp edges AlternateSwitches Mayusethefollowing Checkwithlocalauthoritiesandelectrician CLIPSAL 203 2E45 OUD Dimmer CLIPSAL 2031 VF3CSF 3 Speed CAUTION Labelallwirespriortodis connection when servicing controls Wiringerrorscancauseimproperand dangerous operation Wire Nut Wire Nut Wire Nut Rheostat Wire Nuts Wire Wire Brown Hot Blue Neutr...

Страница 36: ...he right side of the Log 1 There are 2 landing spots on the burner to rest Log 2 into lean the top portion of Log 2 on Log 1 4 Place Log 4 in the landing spot in the burner located in between Logs 2 3 as shown in Diagram 4 3 Place Log 3 diagonally as shown below The top part of Log 3 will rest in the landing spot on Log 1 and the bottom portion will rest in a landing spot in the burner Description...

Страница 37: ...de of Log 1 as shown in Diagram 9 9 Line up the pin locators on Log 9 with the pins in Log 1 and Log 7 as shown in Diagram 10 10 Place Log 10 in the landing spot in the burner located on the far right side of Log 1 facing Side B as shown in Diagram 11 Place embers on burner locations show in Diagram 12 6 Side B Place Log 6 in the landing spot in the burner located on the far right side of Log 1 as...

Страница 38: ...hown below to remove front trim piece 3 Reverse steps to reinstall 1 Remove front trim piece see instructions above 2 Remove two 2 screws in locations shown below to release panel clips 3 Remove panels by sliding out 4 Reverse steps to reinstall Front Trim Piece Panel Clip Screw Locations Panel Clip Diagram 1 Front Trim Screw Locations END PANEL REMOVAL INSTALLATION FRONT TRIM REMOVAL INSTALLATION...

Страница 39: ...frame overlay out of the 3 so that the faceplate anddoorframeoverlayareflushwithoneanother SeeDiagram2 1 Install the fascia to the unit by hooking the left and right side mounting brackets into the mounting slots at the side of the firebox as shown below Diagram 3 Deflector Installed 3 Hook the inner door frame to the unit Refer to Screen and Inner Door Frame Installation in the manual prior to in...

Страница 40: ...m 1 3 Install Screen and Inner Door Frame to unit but hanging over glass door frame as shown in Diagram 3 Lower gently once in position over glass door frame 4 Repeat on opposite side 2 Bend Tab on Screen Mesh to 90º as shown in Diagram 2 Secure to Inner Door Frame with one 1 screw as shown in Diagram 2a Diagram 1 Diagram 3 Diagram 2 Diagram 2a ...

Страница 41: ...on OPTIONAL FINISHING TRIM INSTALLATION 1 Install the optional finishing trim by lining up trim with the outside of the fascia Press trim inward firmly to seat onto the unit 2 Pull trim outward away from the unit to remove Finishing Trim Installed ...

Страница 42: ...rner will always start on HIGH and resume it s last setting after 20 seconds of operation NOTE When the glass is cold and the appliance is lit it may cause condensation and fog the glass This condensation is normal and will disappear in a few minutes as the glass heats up DO NOT ATTEMPT TO CLEAN THE GLASS WHILE IT IS STILL HOT DO NOT BURN THE APPLIANCE WITH OUT THE GLASS FRONT IN PLACE SUMMARY OF ...

Страница 43: ...ATE INSTRUCTIONS WARNING DO NOT SPRAY AEROSOLS IN THE VICINITY OF THIS APPLIANCE WHILE IN OPERATION Appliances incorporating a live fuel effect designed to oper ate with blue flames with slight yellow tips may exhibit slight carbon deposition FOR YOUR SAFETY READ BEFORE LIGHTING A BEFORE LIGHTING smell all around the appliance areaforgas Besuretosmellnexttothefloorbecause some gas is heavier than ...

Страница 44: ...ns in this manual 2 Remove logs 3 Remove burner side panels by lifting out as shown in Diagram 1 4 Removeburnerbyremoving2screwsinlocationsshownbelowinDiagram2 5 Remove end panels see instructions in this manual 6 Remove 11 screws to remove fan access panels as shown in Diagram 3 7 Remove 2 screws to release fan bracket Diagram 1 Burner Side Panels Diagram 2 Burner Screw Locations tooltip tooltip ...

Страница 45: ...pection of the flueing system semi annually Recommended areas to inspect as follows 1 Check the Flueing System for corrosion in areas that are exposed to the elements These will appear as rust spots or streaks and in extreme cases holes These compo nents should be replaced immediately 2 Remove the termination cap and shine a flashlight down the Flue Remove any bird nests or other foreign material ...

Страница 46: ...ite igniter continues to spark for 30 sec ondes then goes to lockout Crossed polarity or faulty sensor lead circuit Faulty extension lead or power board Check polarity at power point connection into heater and control box Remove or replace extension lead or power board Unit ignites main burner becomes unstable flame lifts off burner unit goes into lockout Flue blocked Incorrect flue installation o...

Страница 47: ...sert the door tool into the lower door latch on Side B 1 Remove 3 screws from Side A in the locations shown below WARNING Do not operate the appliance with the glass panels removed cracked or broken Replacement of the glass panels should be done by a licensed or qualified service person Glass should be cool if cleaning is necessary Door Tool Upper Door Hooks Lower Door Latches There are 2 glass do...

Страница 48: ... panels on one side see instructions in this manual 2 Remove logs 3 Remove burner side panels by lifting out as shown in Diagram 1 4 Remove burner by removing 2 screws in locations shown below Diagram 1 Burner Side Panels Diagram 2 Burner Screw Locations tooltip tooltip 5 Slide burner to the left and lift out 6 Remove 12 screws securing valve tray 7 Lift out valve tray to remove 8 Replace with new...

Страница 49: ...N A N A N A N A N A N A N A N A 910 084 Control Box N A N A N A 911 101 Control Box N A N A N A N A N A N A N A 911 227 Control Box N A N A N A N A N A N A N A N A 910 527 Manual Control Switch N A N A N A N A N A N A 910 080 Valve 910 521 Control Box Cable 1 910 522 Control Box Cable 2 910 523 Control Box Cable 3 910 525 Control Box Cable 4 N A 2 1 1 3 N A 2 N A N A 910 912 Ignition Module to Val...

Страница 50: ... IV N S 911 112 Pressure Swtch MPL 9370 0 20 DEACT N S 911 113 Switch On Off W CAT 5 Cable 3 FT 105C N S 911 121 Module SIT 230V DV 0 579 204 N S 911 183 SwitchPushButtonResetECS Round N S 296 122 Spring Door 7 in x 0 5 in N S 396 042F Plate Slide Door Frame Tool N S 936 157 GasketTadpoleTape Alum F Core sold per 25 4 mm 629 mm required N S 904 691 Glass U clips Each N S 696 930 Log Set Complete N...

Страница 51: ...Regency GF1500LST Gas Fireplace 51 PARTS LIST parts list MAIN ASSEMBLY SIDE A SIDE B ...

Страница 52: ...ription 32 606 922 Inner door frame Black w Screen 606 932 Inner door frame Stainless w Screen 33 606 544 Door Frame Overlay Black 34 606 938 Fascia and Door Frame Black w Screen 606 936 Fascia and Door Frame Stainless Steel w Screen 606 951 Fascia Black Glass not shown 32 33 34 ...

Страница 53: ...Regency GF1500LST Gas Fireplace 53 NOTES notes ...

Страница 54: ... components Ignition Control Boards Wiring Switches Fans Fan Control Module Battery Pack Remote Control Systems 1 Enamel Panels 1 Venting Venting Components 1 All Stainless steel surrounds 1 All Firebox Media Crystals Fire beads Volcanic Ceramic Spa Stones 1 All hardware 1 Mesh Glass Safety Barriers 1 Accent Light Bulbs 1 Glass Crazing 1 After the original warranty coverage for any of the parts ab...

Страница 55: ... general practice of FPI to charge for larger higher priced replacement parts and issue credit once the replaced component has been returned to FPI and evaluated for manufacturer defect If a consumer has a unit installed outside an accredited distributor dealer or pre approved service agent s service area or the closest approved service agent is situated more than thirty 30 kilometres from the ins...

Страница 56: ...r movement expansion and contraction of the steel is normal and is not covered under the terms of this warranty Freight damages for products or parts are not covered under the terms of the warranty Porcelain Enamel Absolute perfection is neither guaranteed nor commercially possible Any chips must be reported and inspected by the authorised selling dealer within three 3 days of installation Any dam...

Страница 57: ... to at the option of the supplier one or more of the following i replacement of the goods or the supply of equivalent goods ii the repair of the goods iii the payment of the cost of replacing the goods or of acquiring equivalent goods or iv equivalent goods or v the payment of the cost of having the goods repaired b To the extent that services supplied by the supplier are services other than servi...

Страница 58: ...services Fireplace Products Australia Pty Ltd 1 3 Conquest Way Hallam VIC Australia 3803 Phone 61 3 9799 7277 Fax 61 3 9799 7822 To obtain warranty service in Western Australia and or New Zealand please contact one of our authorised distributors in those areas Western Australia Air Group Australia 28 30 Division St Welshpool WA Australia 6106 Phone 08 9350 2200 Fax 08 9353 4225 New Zealand Aber Ho...

Страница 59: ...er the warranty for you It is important you provide us with all the information below in order for us to serve you better Warranty Registration Form or Register online immediately at the above Web Site Warranty Details Serial Number required Purchase Date required mm dd yyyy Product Details Product Model required Dealer Details Dealer Name required Dealer Address Dealer Phone Installer Date Instal...

Страница 60: ......

Страница 61: ...Regency GF1500LST Gas Fireplace 61 NOTES notes ...

Страница 62: ...62 Regency GF1500LST Gas Fireplace NOTES notes ...

Страница 63: ......

Страница 64: ...ler Name Address _______________________________________________ ___________________________________________________________________ Installer ____________________________________________________________ Phone ____________________________________________________________ Date Installed _______________________________________________________ Serial No ________________________________________________...

Отзывы: