Electrical connections/Operating modes
RESTART (MANUAL OPERATION)
The choice between MANUAL or AUTOMATIC mode of operation is possible thanks to the SAFEGATE
CONFIGURATOR software. In Manual mode Pin 10 has RESTART function.
As a result of occupation of the protected area, outputs will be deactivated (start/restart interlock enabled).
Î
To reactivate OSSDs it needs to press and release the N.O. RESTART pushbutton connected to 24VDC.
Verify the logical sequence: 0 → 1 → 0.
¾
The high level (24Vdc) time must be between 100 ms and 5 s.
Use in manual mode (start/restart interlock enabled) is mandatory in case the safety device
controls a gate to protect a dangerous area and a person, once crossed the gate, can stay
in the hazardous area without being detected (use as a ‘trip device’ according to IEC 61496).
The Restart command must be located outside the hazardous area, at a point where the
hazardous area and the entire working area concerned are clearly visible.
It must not be possible to reach the command from inside the hazardous area.
AUTOMATIC OPERATION
The choice between MANUAL or AUTOMATIC mode of operation is achieved thanks to the SAFEGATE
CONFIGURATOR software.
In Automatic operating mode, the OSSD1 and OSSD2 safety outputs follow the status of the light curtain:
¾
with guarded area free, the outputs are ON.
¾
with guarded area occupied, the outputs are OFF.
If the SAFEGATE light curtain is used in AUTOMATIC mode, it will not be equipped with
a start/restart interlock circuit. In most applications, this safety function is mandatory.
Carefully evaluate the risks analysis of your own application.