Door control
FireProV2
Manual
Please keep this manual with attachments carefully!
42
12.3
Common Errors
Notification Description
Recommendation/explanation
F 3.1
Door past limit switch
closed
hold the open button on the circuit board for at
least 5 seconds, after this 5 second the door/roller
shutter will open when holding this button Hold to
run open and can be set back between the final
positions.
Watch out!
This function does not monitor the end positions,
direction of rotation and movement. Do not allow
the door to move further then partial opening,
with a correct direction of rotation.
F 1.3+5.5
DES not recognized
Press the middle (sw2) and bottom (sw3) menu
buttons on the print at the same time and hold it
for 3 seconds
Parameter 0.9 now appears
Change value from parameter 0.9 to :
0 = Automatic or
1 = DES
GFA
Watch out! The change in value must be done
quickly because the time for this is limited.
Press
SW2, control starts again.
Should this not produce the desired result,
disconnect the DES connector on the circuit board
under voltage and reconnect it under voltage.