Door control
FireProV2
Manual
Please keep this manual with attachments carefully!
41
F 4.6
Light curtain activated
Light curtain is activated. Photocell entrance
interrupted. Make sure the beam of light is not
interrupted. Whether the light curtain is properly
connected and is not faulty. Check parameter 5.1,
5.2 or 5.3, if light curtain has been chosen. If no
light curtain is connected, disable it at the
appropriate parameter.
F 4.7
Light curtain defect
Test function of the light curtain negatively.
Check the light curtain. Check connections.
Replace in case of malfunction. Test function
should be activated by the selected output in menu
5. Check parameter 5.1, 5.2 or 5.3, if light curtain
has been chosen. If no light curtain is connected,
disable it at the appropriate parameter.
F 5.1
Error in Rom memory
Rom memory check failed. Restart the controls, if
this does not work, switch off the controls.
F 5.5
DES (digital limit switch)
error
Cannot communicate with Digital switch. Check
the connections of digital limit switch at X5.
Check the power supply for the DES at X5
conne12V and GND. Check the
connections X5 A and B. Switch the digital limit
switch of the motor if it is defective.
F 5.6
Door movement error
Check the door mechanically.
F 5.7
Error in direction of rotation
Direction of rotation has been changed after
entering the end positions. Make sure that the door
opens with the up button if this is not the case,
reset the control to factory setting with parameter
9.5 of the menu. And re-learn the end positions.
If the motor has the wrong direction of rotation,
switch connection U and W
at connector
X2
( Fig.5) to change the direction of rotation of the
motor.
F5.9
Duration monitoring
Maximum duration exceeded. Check the
door/roller shutter mechanically. Verify that the
time set at parameter 2.1 is sufficient and adjust it
if necessary.
F 7.0
No power supply available
This notification appears if the mains power is not
present. The control only works on the batteries.
The door can no longer be operated. This will only
close if the fire, smoke alarm contact is activated
or if it is chosen to close at low battery voltage. If
the batteries are completely empty, the door will
also close, but then the protections and limit
switch will no longer work.
F 7.1
Low battery voltage or 24V
overloaded
This notification is displayed when the voltage of
the batteries comes under the in the menu set level,
or if the power supply collapses due to overload.