Door control
FireProV2
Manual
Please keep this manual with attachments carefully!
36
11.5
Parameter settings 4. :
Parameter
Description
Settings
4.1
Action at fire alarm
NES:
1
.1 Door/roller shutter immediately completely
closed
.2 Stop at additional limit switch (S6)
Then close at
set
time ( parameter 4.2)
(not possible if parameter 3.1 is on 2)
DES:
.1 Door/roller shutter immediately completely
closed
.2 Stop at additional limit switch
Then close at
set
time ( parameter 4.2)
( set via parameter 1.7)
4.2
Waiting time at
additional stop
(Parameter 4.1 on .2
)
1 t/m 240 seconds
1
4.3
Function smoke
detection.
NES:
1
.1 Close completely
.2 Partial opening
For partial
opening, the door is sent to
position of S6.
Parameter 3.1 may not be set to .2
DES:
.1 Close completely
.2 Partial opening
For partial
opening, the door is sent to position
set with parameter 1.7. Parameter 1.7 must be
set before option .2 can be selected
4.4
Function
no
Phase 1
or Zero(N)
present.
(if parameter 4.3 option
".2 is chosen).
NES:
1
.1 Stays at current position if door/roller
shutter is not open at the end position. Close to
intermediate position at end position.
.2 Close completely if it is below the position
set on S6
DES:
.1 Door/roller shutter remains standing if it is
below the position set at 1.7.
.2 Door closes completely if it is below the
position set.
4.5
Disable operation after
reset smoke detection.
0 t/m 240 seconds
60
sec.