7 Description of Control Unit
The FirePro is a controller for failsafe drives (FS series) with mechanically adjustable limit
switches (NES) or digital Absolute Encoder (DES) and centrifugal brake. This control unit can
work both automatically and in hold to run. The operation is possible with the control buttons on
the cabinet and by means of external up-stop-down control. There is also an input for an impulse
control (e.g. pull switch) available.
A two-color LED is present on the lid which is green in normal operation and is red in case of
malfunction, fire alarm, smoke detection or power failure. The notification belonging to the red
LED is displayed on the control print display.
There is an input for the safety contact (NC) of the safety brake. If this entry is interrupted, the
door can no longer be operated.
The control unit is equipped with batteries that provide the control voltage and hold the brake in
case of a power failure if there is no fire or smoke notification. In the case of fire alarm, smoke
detection or if the batteries are empty or not present, the door will drops because the power supply
for the brake is gone.
When voltage is still present, the door drops until the limit switch is closed
or the "overclose" limit switch is reached. In the menu you can set whether the door is lowered
until the normal limit switch is reached or until the "overclose" limit switch is achieved. With the
"overclose" limit switch a door can possibly drop further than it does during normal operation.
A
Stop
with a set time
can
optionally be made at a desired position, during fire alarm, smoke
detection or low battery voltage. This can only be used with CAM switches when the "overclose"
function is not in use.
7.1
Fire alarm:
After fire alarm, the door is released immediately or after extended time
(parameter 3.4, 0-140
sec.)
.
7.2
Smoke detection:
In the case of smoke detection, a command must be given at the reset entry after the smoke
detection is over. In the case of smoke detection, there is also a potential-free contact indicating
that the door is closed so that the air bellows
for
smoke sealing
can be filled between the door. It
is therefore no longer possible to flee. If this contact is not used for detection, it can be
programmed in the menu to switch if a malfunction is active.
7.3
Siren/Alarm:
When the door is in motion, a potential-free switch can be used to connect a siren or other
signaling. This stops when the door stops moving. in the event of a fire alarm, there is also a
potential-free switch which can also be connected to a siren/alarm or other signaling.
7.4
Safety edge:
It is possible to connect an safety edge. This can be an safety edge by means of DW (air pressure,
1k2) contact, 8k2 safety edge or opto sensors. Under normal operation, the safety edge only works
if automatically Closing is selected. In the event of a fire alarm, smoke detection or low battery
voltage, the safety edge can be switched on or off. If it is switched on, when the safety edge is
activated, the door will stop. The menu allows you to select which safety edge has been chosen
and set the waiting time after the safety edge has been activated before the door continues to drop.
If the power supply is still present, you can also select to fully open the door and then close it
again.