Door control
FireProV2
Manual
Please keep this manual with attachments carefully!
14
9.3
Motor:
The 3 phases or phase and zero of the motor are connected to X2 (U-V-W). With a 1 phase motor,
V is the zero, U is the closing phase and W is the opening phase. The earth can be connected under
X3 and the brake on X17(see Fig. 5).
When connecting the brake, observe the polarity correctly. The positive and negative
may not be changed!
3 Phase 400V
3 Phase 230V
Only with GFA
Connect Motor in star Connect Motor in Triangle
FS 15 WS drive
Figuur 5 Connecting 3 Phase and 1 Phase motor
9.4
Mechanical End Switches:
The cam/mechanical limit switches of the motor are connected to X5. Figure 6 shows the schedule
for connecting the limit switches. The extra limit switch is a NO contact. The other limit switches
are all NC contacts.
Figure 6 Connecting Cams/Mechanical limit Switches