Door control
FireProV2
Manual
Please keep this manual with attachments carefully!
11
8 Mounting
For a solid, professional installation of this control unit, the following points must be checked and
inspected:
1.
The control unit must be fitted in a good, solid housing which meets the necessary
requirements for the situation on the location.
2.
In order to meet the required IP value, the cable glands should be replaced if necessary. If
necessary, further sealing measures should be taken.
3.
PVC insulated cabling should only be applied indoor.
4.
Power supply Phase (1N ~ 230VAC-50Hz, +/-10%) Must be secured with a fuse against
short circuits and overload.
5.
In case of a power cable with a 3-pole 16A CEE plug (phase, Zero & Earth) applies:
assemble a 16A. Socket in the direct proximity of the controller and fuse the power supply
in accordance with applicable standards/guidelines. After installation of the control unit
and the power cable with the wall socket, check that the screw connections are properly
tightened and that everything is properly connected.
6.
In case of a connection to the installation, the following applies: Connect the control unit
to a fixed power supply line and fuse the power supply as indicated earlier. To interrupt
the power supply, a multi-pole switch must be mounted in the immediate vicinity of the
control unit which all Poles should be interrupted when shut-off.
CAUTION: The switch must have a contact opening which complies with the span
CATEGORY III for complete separation.
7.
A hazard analysis of the complete installation must be made by the installer on the
location. Please note that the door or gate is appropriate secured and that it cannot bring
hazard to persons or objects.
8.
The installation must at least comply with the European and local laws and standards. In
accordance with European legislation, an automatic door or gate must comply with the
Machinery Directive 2006/42/EC and in particular the following standards: EN 12445; EN
12453; EN 12635 and EN 13241-1, which makes a declaration of conformity possible.
9.
The door or gate must be protected against passing the final position by means of safety-
limit switches, mechanical attacks or other safety systems.
10.
The technical data of any external components such as: Photo cells, traffic lights or loop
detectors should be monitored. These may not exceed the maximum permissible load on
the control unit.