Door control
FireProV2
Manual
Please keep this manual with attachments carefully!
40
F 2.4
8K2 safety edge activated
The 8K2 safety edge is activated, this may be due
to a obstacle in the door opening. If there is no on
obstacle in the door opening and this notification
continues to appear please check that the
resistance on connector X11 (GND and 1K2/8K2
input) is still 8,2KOhm
F 2.5
8K2 safety edge defect
check the resistance of connector X11 (GND and
1K2/8K2 input) is still 8,2KOhm. Check the spiral
cord for any cable breaks.
F 2.6
1K2 safety edge activated
The 1K2 safety edge is activated, this may be due
to a obstacle in the door opening. If there is no
obstacle in the door opening and this notification
continues to appear please check that the
resistance of connector X11 (GND and 1K2/8K2
input) is still 1,2KOhm
F 2.7
1K2 safety edge defect
Check that the resistance of connector X11 (GND
and 1K2/8K2 input) is still 1.2KOhm. Check the
spiral cord for any cable breaks.
F 2.8
1K2 safety edge test
negative
Check that the resistance of connector X11 (GND
and 1K2/8K2 input) is still 1.2KOhm. Check the
spiral cord for any cable breaks. Check pre limit
switch is correctly and ensure that the safety edge
rubber is pressed sufficiently when the door/roller
shutter is closed.
F 2.9
Opto sensor activated
The opto safety edge has been interrupted. This
can be done through an obstacle in the door
opening. If there is no obstacle and this
notification continues to appear, check if the opto
sensor still see each other. Also check the
connections to X12 (+12V and – for the 12V
power supply and input for the signal). Make sure
the sensors are still working or need to be
replaced.
F 3.1
NES:
Safety chain motor activated
(thermo contact, safety limit
switches or emergency
control)
DES:
Emergency limit switch
activated.
NES:
Make sure that the emergency limit switches (red
cams) are activated. If this is the case, check that
the open and closed limit switches are set
correctly. It may also be that the thermo contact of
the motor is activated. Then wait for the motor to
cool down.
DES:
The door is outside the set limit switch range. If
DES is not recognized and the control on changes
to NES,
reset the control via parameter 0.9 and set
it to the correct DES type.