10.3 Bushing tap insulation test
The following picture illustrates measurement setup for tap insulation test of a bushing. In this
method the insulation between tap electrode and ground flange which includes C2 can be
measured. This method can be used only for condenser types bushings with tap electrode.
For this test the GSTg A+B mode should be selected.
Please note that the test voltage must not exceeds the permissible level which defined by bushing
manufacturer. If the permissible maximum test voltage is not clear, do not adjust the output voltage
more than 500 V.
90315-1.2 Instruction Manual CAPO
Page 91 of 117
WARNING !
WARNING !
In bushing tap insulation test, the test voltage must not exceeds the
permissible level which defined by bushing manufacturer.