8 RE / DD / UM / RE-900 1.0-0
1.5 Routine Testing
In order to ensure that the system is fully operational, and to comply
with the requirements of IS 2189: 1988, the following routine attention is
recommended:
Daily -
Check the panel to ascertain that it indicates normal operation.
If any fault is indicated check that it has been recorded and that the
appropriate actions have been taken, e.g. informing the maintaining
company.
Weekly -
Test at least one detector or call point to confirm the
operation of the panel and the audible alarms. Test a different zone
each week and, if possible, a different device. Keep a record of the
device and zone tested each week. Record and report any
malfunction.
Quarterly -
The responsible person should ensure that every three
months the system is checked by a competent person. Check the
standby batteries and the charger voltage Test at least one device in
each zone to check the panel functions. Check the operation of the
audible alarms and any link to a remote manned centre, Central
Station, etc. Carry out a visual inspection of the installation to check for
alterations or obstructions and issue a certificate of testing.
Annually -
The responsible person should ensure that, in addition to the
quarterly checks, each device on the system is tested and that a visual
inspection is made of the cable fittings and equipment.
Note:
The control panel case should be cleaned periodically by wiping
with a soft, damp cloth.
Do not
use any solvents.
Содержание RE-900
Страница 1: ...RE 900 Fire Alarm Control Panel Installation Commissioning Operating user Manual...
Страница 5: ...4 RE DD UM RE 900 1 0 0 NOTES...
Страница 10: ...9 RE DD UM RE 900 1 0 0 Mother Board Terminals and connectors Power Supply Board Terminals and connectors...
Страница 11: ...10 RE DD UM RE 900 1 0 0...
Страница 20: ...19 RE DD UM RE 900 1 0 0 2 6 Internal Arrangement...
Страница 22: ...21 RE DD UM RE 900 1 0 0 Power Supply Board RE 900 PS...