43 RE / DD / UM / RE-900 1.0-0
EVACUATE Key:
This key is used to energize the external hooters
without actual fire.
ENTER KEY:
This key is used to accept the password during silence, reset
in Fire Condition And also used for the Evacuate. This key is used to
check the all LED’s in panel is in good condition with continues buzzer
tone.
MENU Key:
This key is used to get into the program menu and get
back to the previous menu screen.
ACK. Key:
This key is used to acknowledge the buzzer tone during
the fault and fire condition. This key can be operated with user or
admin password.
5.2 Indications
SYSTEM ON:
This LED will glow when the panel is energized by primary
and standby power. This is the only LED glowing in the normal
monitoring condition. The LCD Display as shown below.
MAINS FAIL:
Whenever the Main Supply (110 - 220v A.C) fails, the Mains
fail LED will be illuminated and it also indicated in LCD with toggle
Buzzer tone. The LCD Display as shown in the figure 22, ‘Mains fail’ will
be displayed in the fault screen.
x
– n
th
no. of fault;
y
– Total no. of fault.
Figure – 22
Fault [ x/y ]
Type of Fault
FIRE ALARM
SYSTEM HEALTHY