35 RE / DD / UM / RE-900 1.0-0
4.2.2.3.2 NAC -2
The NAC2 output can be configured as Continuos,
Temporal, Synchronized & 60 BPM. In Temporal and synchronize
mode the NAC2 Output will be as pulse as shown below. In these
modes all the Sounders will be evacuated simultaneously.
To change the option press ‘Change’ key to toggle
between the options Continuous, Temporal, Synchronized &
60BPM. The NAC’s should be in off condition to change the
options.
4.2.2.4 24V Output
The 24V output can be configured as Resettable or steady.
If four wire detectors are used in the panel, then the 24V DC
output should be configured as Resettable. While resetting the
panel this output will cut off for the 3 seconds. . The default
setting is Steady Output. In this mode screen display as below.
24V Output
Steady
To change the option press ‘#’ key to toggle between the
options Steady and resettable.
4.2.2.5 Common
By selecting the number 4 in the keypad, it enters into the
Common screen. It Displays as follows.
1. Settings
2. Features
3. Advanced
[Common]
By selecting the number 1 in the keypad, it enters into the
Setting mode. It Displays as follows.