33 RE / DD / UM / RE-900 1.0-0
Enter Zone No.? AA
Press # to change
Press Enter to Set
AA = Number of panel to be selected.
4.2.2.1.2 Location Program
By selecting the number 2 in the keypad from setting , it
enters into the location program Mode screen. When
entering into this it will ask the zone number. After entering
the zone number press ENTER key, cursors goes to next line.
Then enter the location using the number / letter key pad,
press ENTER key after entering location.
Enter Zone No.? AA
Press # to change
Press Enter to Set
Zone 1
<Loc. not entered
>
4.2.2.1.3 Wiring
From the Zone Wiring program screen, The zones circuit is
designed for the class-B wiring. The style of wiring can be changed
using this option. The Style of class-B can be changed as Style-B or Style-
C by pressing ‘#’ key from the panel key pad. When you enter into this
mode the screen will be as below.
Type: Wiring
Class : B
(# Edit)
(wiring)