47 RE / DD / UM / RE-900 1.0-0
XX
– n
th
no. of events;
YY
– Total no. of events;
X
– Zone No.
Disabled.
Walk Test:
Disable/W.T LED Blinking identifies the corresponding
Zone, which is under walktest. If this LED is illuminates continuously
then it identifies that particular zone is disabled. The walk test mode
helps the user to test each device in that particular zone by a single
person. During walk test mode, if any Fire is identified, the panel will
be silenced and reset automatically after 4 seconds and 2 seconds
respectively. In case of any other zone fire during this period, it is
considered as actual fire and it comes out from the walk test mode.
The LCD Display is as shown below.
For More than One zone in Walk test fire condition, the screen
as follows,
Note
:
a.
If there is no more testing please ensure that the zone is brought
back to the normal Condition.
b.
During in this mode, the Fire Relay will not be activated while in
fire condition.
c.
If the zone is kept in Walk test mode for 10 minutes with out any
test the panel comes out of the walk test mode automatically.
d.
In other zone gets fire, the walk test mode automatically
removed.
Restoral:
When the zone restored to normal condition from
disable / Walk test mode, the zone which are all in disable/W.T
mode the corresponding LED’s goes off.
WT: Fire [XX/YY]
Zone X
WT: Fire [XX/YY]
1st: aa Zone X Rt: bb
Содержание RE-900
Страница 1: ...RE 900 Fire Alarm Control Panel Installation Commissioning Operating user Manual...
Страница 5: ...4 RE DD UM RE 900 1 0 0 NOTES...
Страница 10: ...9 RE DD UM RE 900 1 0 0 Mother Board Terminals and connectors Power Supply Board Terminals and connectors...
Страница 11: ...10 RE DD UM RE 900 1 0 0...
Страница 20: ...19 RE DD UM RE 900 1 0 0 2 6 Internal Arrangement...
Страница 22: ...21 RE DD UM RE 900 1 0 0 Power Supply Board RE 900 PS...