14 RE / DD / UM / RE-900 1.0-0
2.2 Specification
AC Power
110 - 220 VAC, 50 Hz, +10%, -15%.
Wire size: 1.5 Sq. mm with 600 V insulation
Standby power
24VDC as required
Operating Condition:
Operating Temperature 0 - 49° C/32-120° F.
Relative Humidity 93 ± 2% RH (noncondensing)
at 32 ±2° C/90 ±3° F.
Battery (Lead Acid only)
Constant Voltage – 28.0v± 0.5V
Charging Current as required
Charging Capacity: 7 Amp Hour Battery
(Higher size are request)
.
System Quiescent Current: 50mA + (4.4 – 6.8mA per zone)
D.C. output
Operating Voltage: 24VDC(Resettable / Steady), 500mA Max.
Initiating Device Circuits (Zone Circuit)
All zones are Class B, Style B / C operation
Normal Operating Voltage: 14 - 24 VDC
Alarm Current: 15 – 35mA threshold
Short Circuit Current: 45mA Maximum
Loop resistance: 100 ohms Maximum
End-Of-Line Resistor: 4K7, 1/2 watt
Standby Current: 7 mA (2.5 mA for Detectors)