over the network in order to check whether the respective slave is still on. When the RB
response from the slave to this RB packet is not received over the Radio channel within
the set RB timeout, i.e. the respective slave is out of order, the central RipEX stops local
answering to RB packets from the master for the respective slave.
○
RB Net period [s]
Default = 10
The RipEX responds to the RB packets locally and in the set RB period the RB packets
are transferred over the network.
○
RB Net timeout [s]
Default = 10 (maximum=8190)
Whenever an RB packet is sent over the network, the set RB Net timeout starts. When
the RB response from the remote unit (slave) is not received within the timeout, i.e. the
respective slave is out of order, the central RipEX stops the local answering to RB packets
from the master for the respective slave.
○
○
Local simulation RB
List box: Off, On
Default = Off
The RP570 Slave expects to receive RB packets from the Master. When the Local simu-
lation RB on the Master is On, the RB packets are transferred over the Radio channel
only in the RB Net period (see Master settings). The Local simulation RB has to be set
the same (On or Off) on all sites in the network, i.e. on the master as well as all slaves.
If
On
, the RipEX generates RB packets locally and transmits them over the COM interface
in the RB Request period and expects the RB response for each RB packet from the
RP570 Slave within the RB Response timeout. When the RipEX does not receive the
response(s) from the RP570 slave, the RipEX does not respond to the RB packet from
the Master which it receives over the Radio channel.
○
RB Request period [ms]
Default = 200 (maximum=8190)
RipEX sends locally RB packets to the connected RTU in the set period.
○
RB Response timeout [ms]
Default = 500 (maximum=8190)
The RipEX expects a response to the RB packet within the set timeout. If it is not received,
the RipEX does not respond to RB packets from the Master received over the Radio
channel.
○
RTU address (Hex)
Default = 01
Active only when the Local simulation RB is On. The connected RTU’s address is sup-
posed to be filled in. This address (0x00-0xFF) is used in the RB packets generated locally
in the RipEX and transmitted over the COM.
■
Siemens 3964(R)
RipEX Radio modem & Router – © RACOM s.r.o.
156
Advanced Configuration
Содержание RipEX
Страница 2: ......
Страница 42: ... DQ Data Quality Min 180 PER Packet Error Rate Max 5 RipEX Radio modem Router RACOM s r o 42 Network planning ...
Страница 222: ...Fig 10 3 ATEX Certificate RipEX 2 3 RipEX Radio modem Router RACOM s r o 222 Safety environment licensing ...
Страница 223: ...Fig 10 4 ATEX Certificate RipEX 3 3 223 RACOM s r o RipEX Radio modem Router Safety environment licensing ...