List box: COM1,COM2, TS1-TS5, MBTCP, Manual.
This UDP port is used as the destination UDP port in UDP datagram in which serial
SCADA packet received from COM1(2) is encapsulated. Default UDP ports for COM1,
COM2 or Terminal servers 1-5 (TS1-TS5) or Modbus TCP (MBTCP) can be used or
UDP port can be set manually. If the destination IP address belongs to a RipEX and
the UDP port is not assigned to COM1(2) or to a Terminal server or to any special
daemon running in the destination RipEX, the packet is discarded.
Table
The Address translation is defined in a table. There are no limitations such as when the
Mask translation is used. If there are more SCADA units on RS485 interface, their "Protocol
addresses" should be translated to the same IP address and UDP port pair, where the
multiple SCADA units are connected. There are 3 possibilities how to fill in the line in the
table:
− One "Protocol address" to one "IP address" (e.g.: 56 ===> 192.168.20.20)
− Interval of "Protocol addresses" to one "IP address" (e.g.: 56 – 62 ===> 192.168.20.20)
− Interval of "Protocol addresses" to interval of "IP addresses" (e.g.: 56 – 62 ===>
192.168.20.20 – 26). It is possible to write only the start IP and dash, the system will add
the end address itself.
Protocol address
This is the address which is used by SCADA protocol. It may be set either in Hexa-
decimal or Decimal format according the List box value.
Protocol address length can be 1 Byte, only for some protocols, e.g. DNP3 and UNI
can also be 2 Bytes.
IP
IP address to which Protocol address will be translated. This IP address is used as
destination IP address in UDP datagram in which serial SCADA packet received from
COM1(2) is encapsulated.
UDP port (Interface)
This is UDP port number which is used as destination UDP port in UDP datagram in
which the serial SCADA message, received from COM1(2), is encapsulated.
Note
You may add a note to each address with your comments up to 16 characters (UTF8
is supported) for your convenience. (E.g. " Remote unit #1 " etc.). Following characters
are not allowed:
" (Double quote)
` (Grave accent)
\ (Backslash)
$ (Dollar symbol)
; (Semicolon)
Active
You may tick/un-tick each translation line in order to make it active/not active.
Modify
Edit Delete Add buttons allow to edit or to add or to delete a line. The lines can be
sorted using up and down arrows.
Slave
RipEX Radio modem & Router – © RACOM s.r.o.
148
Advanced Configuration