Section IX – Technical data
Quincy Vacuum Pump-QSV Series 111
For a cable of 25 mm², B2 at 45 °C, the maximum current is 63 A x 0.8 = 50.4 A. So 2 parallel cables
of 3 x 25 mm² + 25 mm² are sufficient.
Install 50 A fuses on each cable instead of 100 A.
Cable sizing according UL/cUL
Calculation method according UL 508A, table 28.1 column 5: allowable ampacities of insulated copper
conductors (75°C (167°F)).Maximum allowed current in function of the wire size
AWG or kcmil
Maximum current
10
< 30 A
8
< 50 A
6
< 65 A
4
< 85 A
3
< 100 A
2
< 115 A
1
< 130 A
1/0
< 150 A
2/0
< 175 A
3/0
< 200 A
Calculation method for UL:
Single supply cables (3 1 PE - configuration (1)):
Add 25% to the total current from the tables (see UL 508A 28.3.2: “Capacity shall have 125% of the full
load current”)
Install the prescribed maximum fuse on each cable
Parallel supply cable (2 x 3 2 PE - configuration (2)):
Add 25% to the total current from the tables and divide by 2
Multiply the capacity of the cables with 0.8 (see UL 508A table 28.1 continued)
Install fuses of half the size of the recommended maximum fuse size on each cable.
When using 2 x 3 phase + 2 PE as in (3):
Add 25% to the total current from the tables and divide by
√3
Multiply the capacity of the cables with 0.8 (see UL 508A table 28.1 continued)
Fuse size: the recommended maximum fuse size divided by
√3 on each cable.
Size PE cable:
For supply cables up to AWG8: same size as the supply cables
For supply cables larger than AWG8: use maximum allowed capacity.
< 100 A: use AWG8
< 200 A: use AWG6
< 300 A: use AWG4
Always check the voltage drop over the cable (less than 5 % of the nominal voltage is
recommended).Example of supply cable calculation: Itot= 128 A, maximum ambient temperature is 45 °C,
recommended fuse = 150 A.
Single supply cables (3 1 PE - configuration (1)):
I = 128 A + 25 % = 128 x 1.25 = 160 A
Содержание QSV 2200
Страница 1: ...Quincy Oil sealed rotary screw vacuum pumps QSV 2200 QSV 2700 QSV 3200 Instruction Manual...
Страница 2: ......
Страница 4: ...This page intentionally left blank...
Страница 14: ...Section II General description 14 Quincy Vacuum Pump QSV Series Open view front Open view back...
Страница 61: ...Section IV Installation Quincy Vacuum Pump QSV Series 61 Installation 4 1 Dimension drawings...
Страница 62: ...Section IV Installation 62 Quincy Vacuum Pump QSV Series 4 2 Installation proposal...
Страница 119: ...Section XII Declaration of conformity Quincy Vacuum Pump QSV Series 119 Declaration of conformity...
Страница 122: ...Notes 122 Quincy Vacuum Pump QSV Series...
Страница 123: ......
Страница 124: ...www quincycompressor com No 6996 0227 39 2017 09 Printed in USA...