Entering Initial Installation Information
7.3.6.5 Advanced Settings
• Adjust grid protection setpoints
(Configurable grid protection setpoints depend on the selected grid regulation.)
• [AU] 10 Min Voltage
If the average system voltage for 10 minutes exceeds the detection level, the inverter is blocked from the
system within 3 seconds.
• [AU] Active Power Frequency
•
When frequency decreases
: When frequency
decreases below f
LLCO
during ESS charging operation,
the inverter responds in 2 levels depending on
frequency.
-
Level 1
: It decreases charging active power of ESS
until frequency reaches f
Stop_CH
.
-
Level 2
: If frequency decreases more than f
Stop_CH
, it
increases active power output until it reaches f
Pmax
.
•
When frequency increases
: When frequency
decreases below f
LLCO
during ESS charging operation,
the inverter responds in 2 levels depending on
frequency.
-
Level 1
: If frequency exceeds f
ULCO
, ESS linearly
decreases electric power output until it reaches
f
Transition
.
-
Level 2
: If frequency exceeds F
Transition
, it increases
charging active power according to the increase in
frequency until it reaches f
Pmin
.
•
f
Pmax
[Hz]
: Frequency where power output level is maximum
•
f
Stop_CH
[Hz]
: Frequency where power output level is zero
•
f
LLCO
[Hz]
: Lower limit of continuous operation range
•
f
ULCO
[Hz]
: Upper limit of the continuous operation range
•
f
Transition
[Hz]
: Frequency where power output level is zero
•
f
Pmin
[Hz]
: Frequency where power input level is minimum
Parameter
Australia A
Australia B
Australia C
New Zealand
258 V
Detection Level
244 V to 258 V
258 V
258 V
249 V
Default Values
Range
Parameter
Australia A
Australia B
Australia C
New Zealand
48
49
49.75
50.25
50.75
52
f
Pmax
[Hz]
f
Stop_CH
[Hz]
f
LLCO
[Hz]
f
ULCO
[Hz]
f
Transition
[Hz]
f
Pmin
[Hz]
47 to 49
48 to 49.5
49.5 to 49.9
50.1 to 50.5
50.5 to 52
51 to 53
48
49
49.85
50.15
50.75
52
47
48.25
49.5
50.5
51.75
53
48
49
49.8
50.2
51
52
Default Values of Frequency Response Limits
Range
INVER
TER PO
WER LE
VEL (%P )
Po
wer Input
Po
wer Output
f
Pmax
f
stop-ch
f
LLCO
100
47.0
FREQUENCY (Hz)
49.5
48.0
48.5
49.0
49.5
50.0
50.5
51.5
−
100
0
MA
X
INVER
TER PO
WER LE
VEL (%P )
f
ULCO
f
Transition
f
Pmin
100
49.0
FREQUENCY (Hz)
49.5
50.0
50.5
51.0
51.5
52.0
52.5
−
100
0
MA
X